Connection of detectors Labor Strauss
Chapter 3 • ADM technology
173
3.12.6
Sounder FI700/FB/MT/SOUW
3.12.6.1 Connection
3.12.6.2 Tone setting
On the base sounder there are switches by means of which the sound level and the tone can be set.
Three tones are listed here as examples.
The switch settings result in the following
Sound A,
which can be assigned in PARSOFT:
Switch
SW1
SW2
SW3
Frequency [Hz]
Repetition
Application
1- ON
1- ON
1- ON
910
Continuous tone
BS tone
0- OFF
1- ON
1- ON
500 – 1200
3.5s increasing, 0.5s silent Slow whoop
1- ON
1- ON
0- OFF
1200 – 500
1Hz
DIN tone
The switch settings result in the following
Sound B/Sound C
, which can be assigned in PARSOFT:
Switch
SW1
SW2
SW3
Frequency [Hz]
Repetition
Application
1- ON
1- ON
1- ON
910 / 685
2Hz (250ms / 250ms)
BS tone
0- OFF
1- ON
1- ON
910
Continuous tone
BS tone
1- ON
1- ON
0- OFF
910
Continuous tone
BS tone
SW4
Sound level
1 - ON
High – 90dB(A)
0 - OFF
Low – 80dB(A)