42
Chapter 2 • Conventional technology
Connection of detectors Labor Strauss
2.9
Connection of special detectors
2.9.1
Flame Detector Series 16000
2.9.1.1 Settings
The detector can be adapted to different operating conditions by means of DIP switches. The response
time can be selected with DIP switches 6 and 7.
Type
EN 54-10 Class 1
SW6
SW7
Response time
16581
IR2
0
0
8s
16589
IR3
1
0
4s
16591
UV/IR2
0
1
2s
1
1
1s
2.9.1.2 Connection
Connection-LST.odt / 2009 / AN9161298
200/42