Chapter 2 • Conventional technology
Connection of detectors Labor Strauss
2.2
Connection of manual call points
The following manual call points can be connected to a conventional detector interface of the fire detec-
tion control panel:
Description
Type
Manual Call Point Series HFM/HM
HxM/x/11/xx
Manual Call Point Series HFM/HM – 1 auxiliary contact HxM/x/12/xx
Manual Call Point Series HME
HME/FFFF/11/TT/LL/x
Manual Call Point Series HME – 1 auxiliary contact
HME/FFFF/12/TT/LL/x
Manual Call Point/Red/Standard
UNI3021C
Manual Call Point Series C31
C31
Each manual call point has a built-in alarm resistor (R = 1kOhm/0.35W). In the last manual call point,
an end-of-line resistor (Rab = 5.6kOhm) has to be installed.
The end-of-line element can be changed in the parameter setup of the Fire Detection Control Panel
(BC06/BC016/BC600). The factory setting is Rab = 5.6kOhm.
All diodes that are not denoted are of type 1N4004.
2.2.1
Connection of HFM/HM
Old version of the Manual Call Points HFM/HM
Old manual call points HM/HFM/x/12 can be distinguished from new ones by means of the following
characteristics: at the top left of the componentry, old manual call points HM/HFM/x/12 have a ter-
minal strip with 4 terminals (1 through 4), new ones have a terminal strip with 6 terminals (1 through
6).
Connecting the mains voltage 230VAC to the change-over contacts 7, 8 and 9 is only permissible
for the type HM/HFM/x/12/xx/N (with N standing for mains voltage)! It differs from the type
HM/HFM/x/12/xx in that it has additional covers for the insulation of the mains voltage. The
instructions on the safe use, which can be found in the enclosed packet, must be strictly
observed!
Connection-LST.odt / 2009 / AN9161298