![LST BC016 Series User Manual Download Page 198](http://html1.mh-extra.com/html/lst/bc016-series/bc016-series_user-manual_1944502198.webp)
198
Chapter 4 • Analogue values - Condition of detectors/modules
Connection of detectors Labor Strauss
4.6
Wireless elements
4.6.1
RF Interface – FI7x0/RF/W2W
Value
Meaning
0
Device defective, removed, broken wire or short circuit on the loop
32
Device OK
4.6.2
Wireless manual call point – FI700/RF/MCP
Value
Meaning
0
Device defective, removed from base
32
Device OK (active/not active)
4.6.3
Automatic wireless detectors – FI7x0/RF/O, FI7x0/RF/T, FI7x0/RF/OT
Value
Meaning
0
Detector defective, removed from base
32
Idle
>191
Alarm
4.6.4
Wireless modules
4.6.4.1 Control Module – FI700/RF/M1REL
Value
Meaning
0
Module defective, case open or no external supply for control output
32
Module OK (active/not active)
4.6.4.2 Monitor Module – FI700/RF/M1IN
Value
Meaning
0
Module defective, case open, broken wire or short circuit at the input
32-191
Module OK (idle)
>191
Alarm condition
4.6.5
Wireless sounders, wireless strobes
Value
Meaning
0
Device defective
32
Device OK (active/not active)
4.6.6
RF remote indicator
Value
Meaning
0
Device defective
32
Device OK (active/not active)
Connection-LST.odt / 2009 / AN9161298