Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.8.13
Beam Smoke Detector FR2000
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
An alarm verification according to EN 54-2 Type A is not permissible (in the case of the BC600, the
alarm verification is set through the properties of the zone, and in the case of the BC216 it is set
through the type of zone).
Connection-LST.odt / 2009 / AN9161298
200/134