Chapter 3 • ADM technology
Connection of detectors Labor Strauss
3.11.4
Combi module with four (4) supervised inputs, two (2) supervised outputs and two (2) relay out-
puts
3.11.4.1 Address setting
Detailed information can be found on page 95 in Chapter 3.3: „Address programming of loop ele-
ments“. Each input or output occupies a separate address.
The preset address (X) refers to the first input. The other inputs and the outputs have consecutive
addresses.
Input 1 = X; Input 2 = X+1; Input 3 = X+2; Input 4 = X+3
Supervised Output 1 = X+4; Supervised Output 2 = X+5;
Relay output 1 = X+6; Relay output 2 = X+7
3.11.4.2 Function of the LEDs
A summary LED is available both for the inputs and for the outputs.
For the inputs:
In the idle condition of all inputs, the LED will blink in green.
The LED will blink in red if an input is active.
In case of a fault of an input, the LED will be continuously illuminated in yellow.
For the outputs:
The LED will be continuously illuminated in green when at least one output is active.
In case of a fault of a supervised output, the LED will be continuously illuminated in yellow.
3.11.4.3 Connection of Combi Module FI700/M4IN2OUT2REL
Connection-LST.odt / 2009 / AN9161298
200/168
168