Connection of detectors Labor Strauss
Chapter 3 • ADM technology
155
3.8.33
Thermal Max Detector HT-27121-275
The number of detectors of a zone is not limited since only a thermally controlled, normally open con-
tact (bimetallic strip) is used. (Quiescent current of the detector = 0 mA).
This detector activates at 135°C (275°F) and does not have a light emitting diode.
This connection also applies analogously to the following detectors, because they also do not have a
light emitting diode.
Type
Alarm temperature
27121-0-225
107°C
27121-0-275
135°C
27121-0-325
162°C
27121-0-360
182°C
27121-0-450
232°C
27121-0-600
315°C
27121-0-725
385°C
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
Make sure that the temperature resistance of the connection cable is sufficient.
Connection-LST.odt / 2009 / AN9161298