Chapter 2 • Conventional technology
Connection of detectors Labor Strauss
2.12
Connection of door magnets
When connecting door magnets, please make sure that the nominal current of the relay contact is not
exceeded. Additionally, a separate 24VDC electric circuit and a clamping diode 1N4004 have to be used
for the door magnet.
Connection-LST.odt / 2009 / AN9161298