Connection of detectors Labor Strauss
3.8.30
Thermal Detectors 6295, 6296, 6297 and 6298
3.8.30.1 Notes
A maximum of 32 detectors 629x may be connected to a conventional zone interface.
Type
EN 54-5 Class
6295
57°C – A2S
6296
72°C – B2
6297
87°C – CS
6298
117°C – ES
3.8.30.2 Connection
If the conventional zone module is powered by an external power supply, the country-specific regula-
tions concerning emergency power supply have to be observed.
Make sure that the temperature resistance of the connection cable is sufficient.
Connection-LST.odt / 2009 / AN9161298