42
_ LS ELECTRIC
Fan and Pump
H100
Application Function Group
Application 1 Function Group
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
80
0h1A50
Reference compensation of first aux. motor
Aux1 Ref Comp
0.00~Unit Band
0.00
O
81
0h1A51
Reference compensation of second aux. motor
Aux2 Ref Comp
0.00~Unit Band
0.00
O
82
0h1A52
Reference compensation of third aux. motor
Aux3 Ref Comp
0.00~Unit Band
0.00
O
83
0h1A53
Reference compensation of fourth aux. moto
r
Aux4 Ref Comp
0.00~Unit Band
0.00
O
84
0h1A54
Reference compensation of fifth aux. motor
Aux5 Ref Comp
0.00~Unit Band
0.00
O
90
0h1A5A
Interlock selection
Interlock
0
No
0: No
O
1
Yes
91
0h1A5B
Delay time before running the next main motor when
interlock/auto change occurs at the main motor
Interlock DT
0.1~360.0(Sec)
5.0
O
95
1
Oh1A5F
Selection of Auxiliary motor to display
[AP1-96] [AP1-97]
AuxRunTime Sel
0: Aux 1
0: Aux 1
O
1: Aux 2
2: Aux 3
3: Aux 4
4: Aux 5
96
Oh1A60
Operation time(Day) of Auxiliary motor
selected in [AP1-95]
AuxRunTime Day
0 ~ 65535
O
O
97
Oh1A61
Operation time of Auxiliary motor selected
in [AP1-95] (Hour:Minute)
AuxRunTime Min
00:00 ~ 23:59
00:00
O
98
Oh1A62
Deleting operation time of Auxiliary
motor
AuxRunTime Clr
0
None
0: None
O
1
All
2
Aux 1
3
Aux 2
4
Aux 3
5
Aux 4
6
Aux 5
1
AP1-95~98 is available when MMC and Master Follower functions are performed.
Application 2 Function Group
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
40
O
01
1
0h1B01
Load curve tuning
Load Tune
0
No
No
Δ
1
Yes
02
0h1B02
Load curve: Low Freq
Load Fit Lfreq
Base Freq*15%~Load Fit HFreq
30.00
Δ
03
0h1B03
Current at Low Freq
Load Fit LCurr
0.0~80.0(%)
40.0
Δ
04
0h1B04
Power at Low Freq
Load Fit LPwr
0.0~80.0(%)
30.0
Δ
08
0h1B08
Load curve: High Freq
Load Fit Hfreq
Load Fit LFreq~High Freq
51.00
Δ
09
0h1B09
Current at High Freq
Load Fit HCurr
Load Fit HCurr~200.0(%)
80.0
Δ
10
0h1B0A
Power at High Freq
Load Fit HPwr
Load Fit HPwr~200.0(%)
80.0
Δ
11
0h1B0B
Load curve current
Load Curve Cur
-
-
X
12
0h1B0C
Load curve power
Load Curve Pwr
-
-
X
15
0h1B0F
Pump Clean Setting 1
Pump Clean Mode1
0
None
0: None
O
1
DI Defendant
2
Output Power
3
Output Current
16
0h1B10
Pump Clean Setting 2
Pump Clean Mode2
0
None
0: None
Δ
1
Start
2
Stop
3
Start&Stop
17
0h1B11
Pump clean load setting
PC Curve Rate
0.1~200.0(%)
100.0
O
18
0h1B12
Pump clean reference band
PC Curve Band
0.0~100.0(%)
5.0
O
19
0h1B13
Pump clean operation delay time
PC Curve DT
0.0~6000.0(sec)
60.0
O
20
0h1B14
Pump clean available area holding time
PC Start DT
0.0~6000.0(sec)
10.0
O
21
0h1B15
0operationtimewhenforward/reverseswitching
PC Step DT
0.1~6000.0(sec)
5.0
O
22
0h1B16
Pump clean acceleration time
PC Acc Time
0.0~600.0(sec)
10.0
O
23
0h1B17
Pump clean deceleration time
PC Dec Time
0.0~600.0(sec)
10.0
O
24
0h1B18
Forward step steady time
Fwd SteadyTime
0.0~600.0(sec)
10.0
O
25
0h1B19
Forward step steady frequency
Fwd SteadyFreq
0.00, Low Freq~High Freq
30.00
O
26
0h1B1A
Reverse step steady time
Rev SteadyTime
0.0~600.0(sec)
10.0
O
27
0h1B1B
Reverse step steady frequency
Rev SteadyFreq
0.00, Low Freq~High Freq
30.00
O
28
0h1B1C
Number of forward/
reverse steps during pump cleaning
PC Num of Steps
1~10
2
O
29
0h1B1D
Pump clean cycle monitoring
Repeat Num Mon
-
-
X
30
0h1B1E
Number of repeated pump cleaning
Repeat Num Set
0~10
2
O
1
Set the operation mode to AUTO to configure AP2-01