22
_ LS ELECTRIC
Fan and Pump
H100
Group Drive (DRV)
Code
Comm.
No.
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
9
O
01
0h1101
Target frequency
Cmd Frequency
0.00, Low Freq~High Freq
0.00
O
02
0h1102
Keypad run direction setting
Keypad Run Dir
0
Reverse
O
O
1
Forward
03
0h1103
Acceleration time
Acc Time
0,0-600,0(sec)
20.0
0.75~90kW
O
60.0
110~250kW
100.0
315~500kW
04
0h1104
Deceleration time
Dec Time
0,0-600,0(sec)
30.0
0.75~90kW
O
90.0
110~250kW
150.0
315~500kW
06
0h1106
Run command method
Cmd Source
0
Keypad
1: Fx/Rx-1
Δ
1
Fx/Rx-1
2
Fx/Rx-2
3
RS-485
4
Field Bus
5
Time Event
07
0h1107
Frequency setting method
Freq Ref Src
0
Keypad-1
0: Keypad-1
Δ
1
Keypad-2
2
V1
4
V2
5
I2
6
Int 485
7
Field Bus
9
Pulse
10
1
V3
11
I3
09
0h1109
Control mode
Control Mode
0
V/F
0: V/F
Δ
1
Slip Compen
11
0h110B
Jog frequency
Jog
Frequency
0,00, Low Freq~High Freq
10.00
O
12
0h110C
Jog acceleration time
Jog Acc Time
0,0-600,0(sec)
20.0
O
13
0h110D
Jog deceleration time
Jog Dec Time
0,0-600,0(sec)
30.0
O
14
0h110E
Motor capacity
Motor
Capacity
0
0.2 kW(0.3HP)
Depen dent on motor setting
Δ
1
0.4 kW((0.5HP)
2
0.75 kW(1.0HP)
3
1.1 kW(1.5HP)
4
1.5 kW(2.0HP)
5
2.2 kW(3.0HP)
6
3.0 kW(4.0HP)
7
3.7 kW(5.0HP)
8
4.0 kW(5.5HP)
9
5.5 kW(7.5HP)
10
7.5 kW(10.0HP)
11
11.0 kW(15.0HP)
12
15.0 kW(20.0HP)
13
18.5 kW(25.0HP)
14
22.0 kW(30.0HP)
15
30.0 kW(40.0HP)
16
37.0 kW(50.0HP)
17
45.0 kW(60.0HP)
18
55.0 kW(75.0HP)
19
75.0 kW(100.0HP)
20
90.0 kW(125.0HP)
21
110.0 kW(150.0HP)
22
132.0 kW(220.0HP)
23
160.0 kW(250.0HP)
*
O: Possible to write during operation Δ: Possible to write during stop X: Ban on writing
1
10(V3)~11(I3)’ of DRV-07 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.