H100 _
77
Energy Saving Drive
Peripheral Devices
Voltage
Capacity
(kW)
Circuit Breaker(MCCB)
Leakage Breaker(ELCB)
Magnetic Contactor(MC)
Model
Rated Current(A)
Model
Rated Current(A)
Model
Rated Current(A)
Model
Rated Current(A)
3-Phase 200V
0.75
ABS33c
15
UTE100
15
EBS33c
15
MC-9a
11
1.5
15
15
15
MC-18a
18
2.2
30
15
30
MC-32a
32
3.7
30
15
30
MC-32a
32
5.5
ABS53c
50
UTE100
50
EBS53c
50
MC-50a
55
7.5
ABS63c
60
UTE100
60
EBS63c
60
MC-65a
65
11
ABS103c
100
UTE100
100
EBS103c
100
MC-85a
85
15
100
UTE100
100
100
MC-130a
130
18.5
ABS203c
150
UTE150
150
EBS203c
200
MC-150a
150
3-Phase 400V
0.75
ABS33c
10
UTE100
15
EBS33c
10
MC-6a
9
1.5
10
15
10
MC-6a
9
2.2
15
15
15
MC-9a
11
3.7
15
15
15
MC-12a
13
5.5
ABS53c
50
UTE100
50
EBS33c
30
MC-22b
22
7.5
50
UTE100
50
30
MC-32a
32
11
ABS63c
60
UTE100
60
EBS53c
50
MC-50a
50
15
ABS63c
80
UTE100
80
EBS63c
60
MC-65a
65
18.5
ABS103c
100
UTE100
100
EBS103c
100
MC-85a
85
22
ABS103c
125
UTE150
125
125
MC-100a
105
30
ABS103c
125
UTE150
125
125
MC-130a
130
37
ABS203c
175
UTE250
175
EBS203c
200
MC-150a
150
45
ABS203c
225
UTE250
225
225
MC-185a
185
55
ABS203c
250
UTE250
250
250
MC-185a
185
75
ABS403c
300
UTE400
300
EBS403c
300
MC-225a
225
90
ABS403c
350
UTE400
350
350
MC-330a
330
3-Phase 400V
110
ABS603c
500
UTS600
500
EBS603c
500
MC-400a
400
132
ABS603c
600
600
630
160
ABS603c
630
600
630
MC-630a
630
185
ABS803c
800
UTS800
800
EBS803c
800
220
ABS803c
800
800
800
MC-800a
800
250
ABS1003c
1000
1000
EBS1003b
1000
315
ABS1203b
1200
UTS1200
1200
1200
MC-1200a
1200
355
ABS1203b
1200
1200
EBS1203b
1200
400
-
1600
-
1600
-
-
-
-
500
-
1600
-
1600
-
-
-
-
3-Phase 500V
110
ABS603c
500
UTS600
500
EBS603c
500
MC-400a
400
132
ABS603c
600
600
EBS603c
630
MC-400a
400
160
ABS603c
630
600
EBS603c
630
MC-630a
630
185
ABS803c
800
UTS800
800
EBS803c
800
MC-630a
630
220
ABS803c
800
800
EBS803c
800
MC-800a
800
250
ABS803c
800
800
EBS803c
800
MC-800a
800
315
ABS1203b
1200
UTS1200
1200
EBS1203c
1200
MC-1200a
1200
355
ABS1203b
1200
1200
EBS1203c
1200
MC-1200a
1200
400
-
1600
-
1600
-
-
-
-
500
-
1600
-
1600
-
-
-
-
In accordance with the IEC 60439-1 regulation, symmetrical high current at the maximumrated voltage of the product.
Fuse/Reactor Specifications short-circuit current of the code applicable to the power input part is 100kA. H100 Drive is designed to endure rated 100kA