28
_ LS ELECTRIC
Fan and Pump
H100
Control Function Group (CON)
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
4
O
04
0h1404
Carrier frequency
Carrier Freq
1.0~15.0(kHz)
3.0
0.75~90kW
O
1.0~5.0(kHz)
2.0
110~355kW
1.0~4.0(kHz)
1.5
400~500kW
05
0h1405
Switching mode
PWM Mode
0
Normal PWM
0: Normal PWM
Δ
1
Lowleakage PWM
13
0h140D
Hunting prevention
function used or not
AHR Sel
0
No
1
Δ
1
Yes
14
0h140E
Hunting prevention Pgain
AHR P-Gain
0~32767
1000
O
15
0h140F
Hunting prevention start frequency
AHR Low Freq
0~AHR High Freq
0.5
O
16
0h1410
Hunting prevention end frequency
AHR High Freq
AHR Low Freq~400.00
400.00
O
17
0h1411
Hunting prevention
compensation voltagelimit
AHR limit
0~20
2
O
21
1
0h1415
Auto torque boost filter gain
ATB Filt Gain
1-9999(msec)
10
O
22
0h1416
Auto torque boost voltage gain
ATB Volt Gain
0.0~300.0%
100.0
O
70
0h1446
Speed search mode or not
SS Mode
0
Flying Start-1
0: Flying Start-1
Δ
1
Flying Start-2
71
0h1447
Speed search run or not
Speed Search
Bit
0000~1111
0000
Δ
Bit 0
Speed search
Bit 1
Restart after trips
(other than LV trip)
Bit 2
Restart after instantaneous
interruption
Bit 3
Power-on run
72
2
0h1448
Speed search reference current
SS Sup-Current
50~120(%)
90
0.75~250kW
O
80
315~500kW
73
3
0h1449
Speed search proportional gain
SS P-Gain
0~9999
Flying Start-1 : 100 Flying
Start-2 : Varies according to
the motor type
O
74
0h144A
Speed search integral gain
SS I-Gain
0~9999
Flying Start-1 : 200 Flying O
Start-2 : Varies according to
the motor type
75
0h144B
Output block time before
speed search
SS Block Time
0,0-60,0(sec)
1.0
Δ
77
0h144D
Energy buffering or not
KEB Select
0
No
0: No
Δ
1
Yes
78
4
0h144E
Energy buffering start level
KEB Start Lev
110.0~140.0(%)
125.0
0.75~90kW
Δ
115.0
110~500kW
79
0h144F
Energy buffering stop level
KEB Stop Lev
125.0 ~ 145.0(%)
130.0
0.75~90kW
Δ
125.0
110~500kW
80
0h1450
Energy buffering slip gain
KEB Slip Gain
1~20000
300
O
81
0h1451
Energy buffering P gain
KEB P Gain
1~20000
1000
O
82
0h1452
Energy buffering I gain
KEB I Gain
1~20000
500
O
83
0h1453
Energy buffering acceleration time
KEB Acc Time
0,0-600,0(sec)
10.0
0.75~90kW
O
30.0
110~500kW
1
CON-21~CON-22 codes appear when DRV-15 is set as Auto 2.
2
CON-72 code appears when Flying Start-1is set and when any one bit of CON-71 code is set as 1.
3
CON-73~CON-75 codes appear when any one bit of CON-71 code is set as 1.
4
CON-78~CON-83 codes appear when CON-77 code is set as 1(Yes)