H100 _
53
Energy Saving Drive
Exhaust Fan(MC3) Group
Macro Code
Code
LCD Display
Default
0
-
Jump Code
1 : CODE
1
DRV 3
Acc Time
0.75~90kW
20.0
110~250kW
60.0
315~500kW
100.0
2
DRV 4
Dec Time
0.75~90kW
30.0
110~250kW
90.0
315~500kW
150.0
3
DRV 7
Freq Ref Src
1: Keypad-2
4
DRV 11
JOG Frequency
15.00
5
BAS 7
V/F Pattern
1: Square
6
BAS 70
Acc Time-1
20.0
7
BAS 71
Dec Time-1
30.0
8
BAS 72
Acc Time-2
22.5
9
BAS 73
Dec Time-2
32.5
10
BAS 74
Acc Time-3
25.0
11
BAS 75
Dec Time-3
35.0
12
BAS 76
Acc Time-4
27.5
13
BAS 77
Dec Time-4
37.5
14
BAS 78
Acc Time-5
30.0
15
BAS 80
Acc Time-6
32.5
16
BAS 81
Dec Time-6
42.5
17
BAS 82
Acc Time-7
35.0
18
BAS 83
Dec Time-7
45.0
19
ADV 10
Power-on Run
1: Yes
20
ADV 50
E-Save Mode
2: Auto
21
ADV 64
FAN Control
2: Temp Control
22
ADV 65
U/D Save Mode
1: Yes
23
CON 4
Carrier Freq
3.0
24
CON 70
SS Mode
1: Flying Start-2
25
CON 77
KEB Select
1: Yes
26
OUT 32
Relay 2
10: Over Voltage
Macro Code
Code
LCD Display
Default
27
PID 1
PID Sel
1: Yes
28
PID 3
PID Output
-
29
PID 4
PID Ref Value
-
30
PID 5
PID Fdb Value
-
31
PID 10
PID Ref 1 Src
4: I2
32
PID 11
PID Ref 1 Set
0.5000
33
PID 25
PID P-Gain 1
35.00
34
PID 26
PID I-Time 1
15.0
35
PID 36
PID Out Inv
1: Yes
36
PID 50
PID Unit Sel
5: inWC
37
PID 51
PID Unit Scale
4: x0.01
38
AP1 21
Pre-PID Freq
30.00
39
PRT 8
RST Restart
11
40
PRT 9
Retry Number
0
41
PRT 10
Retry Delay
10.0
42
PRT 11
Lost KPD Mode
3: Dec
43
PRT 12
Lost Cmd Mode
3: Hold Input
44
PRT 40
ETH Trip Sel
1: Free Run
45
PRT 42
ETH 1min
120
46
PRT 52
Stall Level 1
130
47
PRT 70
LDT Sel
1: Warning
48
PRT 72
LDT Area Sel
0: Output Current
49
PRT 75
LDT Band Width
10% of max. value of LDT source
50
PRT 76
LDT Freq
10.00
51
PRT 77
LDT Restart DT
300.0
52
M2 4
M2-Acc Time
10.0
53
M2 5
M2-Dec Time
20.0
54
M2 25
M2-V/F Patt
1: Square
55
M2 28
M2-Stall Lev
110
56
M2 29
M2-ETH 1min
110
Cooling Tower(MC4) Group
Macro Code
Code
LCD Display
Default
0
-
Jump Code
1 : CODE
1
DRV 3
Acc Time
0.75~90kW
20.0
110~250kW
60.0
315~500kW
100.0
2
DRV 4
Dec Time
0.75~90kW
30.0
110~250kW
90.0
315~500kW
150.0
3
DRV 7
Freq Ref Src
1: Keypad-2
4
DRV 11
JOG Frequency
15.00
5
BAS 7
V/F Pattern
1: Square
6
BAS 70
Acc Time-1
20.0
7
BAS 71
Dec Time-1
30.0
8
BAS 72
Acc Time-2
22.5
9
BAS 73
Dec Time-2
32.5
10
BAS 74
Acc Time-3
25.0
11
BAS 75
Dec Time-3
35.0
12
BAS 76
Acc Time-4
27.5
13
BAS 77
Dec Time-4
37.5
14
BAS 78
Acc Time-5
30.0
15
BAS 80
Acc Time-6
32.5
16
BAS 81
Dec Time-6
42.5
17
BAS 82
Acc Time-7
42.5
18
BAS 83
Dec Time-7
45.0
19
ADV 10
Power-on Run
1: Yes
20
ADV 50
E-Save Mode
2: Auto
21
ADV 64
FAN Control
2: Temp Control
22
ADV 65
U/D Save Mode
1: Yes
23
CON 4
Carrier Freq
3.0
24
CON 70
SS Mode
1: Flying Start-2
25
CON 77
KEB Select
1: Yes
Macro Code
Code
LCD Display
Default
26
OUT 32
Relay 2
10: Over Voltage
27
PID 1
PID Sel
1: Yes
28
PID 3
PID Output
-
29
PID 4
PID Ref Value
-
30
PID 5
PID Fdb Value
-
31
PID 10
PID Ref 1 Src
4: I2
32
PID 11
PID Ref 1 Set
50.00
33
PID 25
PID P-Gain 1
40.00
34
PID 26
PID I-Time 1
15.0
35
PID 36
PID Out Inv
1: Yes
36
PID 50
PID Unit Sel
3: °F
37
PID 51
PID Unit Scale
2: x1
38
AP1 21
Pre-PID Freq
30.00
39
AP1 22
Pre-PID Delay
120.0
40
PRT 8
RST Restart
11
41
PRT 9
Retry Number
0
42
PRT 10
Retry Delay
10.0
43
PRT 11
Lost KPD Mode
3: Dec
44
PRT 12
Lost Cmd Mode
3: Hold Input
45
PRT 40
ETH Trip Sel
1: Free Run
46
PRT 42
ETH 1min
120
47
PRT 52
Stall Level 1
130
48
PRT 70
LDT Sel
1: Warning
49
PRT 72
LDT Source
0: Output Current
50
PRT 75
LDT Band Width
10% of max. value of LDT source
51
PRT 76
LDT Freq
10.00
52
PRT 77
LDT Restart DT
300.0
53
M2 25
M2-V/F Patt
1: Square
54
M2 28
M2-Stall Lev
110
55
M2 29
M2-ETH 1min
110