H100 _
29
Energy Saving Drive
Input Terminal Group (IN)
Code Comm. No
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
65
O
01
0h1501
Frequency upon maximuminput by analog
Freq at 100%
Start frequency ~ Max. frequency (Hz)
Max. frequency
O
05
1
0h1505
V1 Input level display
V1 Monitor(V)
0~12.00(V) or -12.00~12.00(V)
0.00
X
06
0h1506
V1 input polarity selection
V1 Polarity
0
Unipolar
0: Unipolar
Δ
1
Bipolar
07
0h1507
V1 input filter time constant
V1 Filter
0-10000(msec)
10
O
08
0h1508
V1 input minimum voltage
V1 Volt x1
0.00~10.00(V)
0.00
O
09
0h1509
Output % at V1 minimum voltage
V1 Perc y1
0.00~100.00(%)
0.00
O
10
0h150A
V1 input maximum voltage
V1 Volt x2
0.00~12.00(V)
10.00
O
11
0h150B
Output % at V1 maximum voltage
V1 Perc y2
0.00~100.00(%)
100.00
O
12
2
0h150C
V1 input minimum voltage
V1–Volt x1’
-10.00~0.00(V)
0.00
O
13
0h150D
Output % at V1 minimum voltage
V1–Perc y1’
-100.00~0.00(%)
0.00
O
14
0h150E
V1 input maximum voltage
V1–Volt x2’
-12.00~0.00(V)
-10.00
O
15
0h150F
Output % at V1 maximum voltage
V1–Perc y2’
-100.00~0.00(%)
-100.00
O
16
0h1510
Changing V1 rotation direction
V1 Inverting
0
No
0: No
O
1
Yes
17
0h1511
V1 quantizing level
V1 Quantizing
0.00
3
, 0.04~10.00(%)
0.04
O
20
4
0h1514
Temperature display
T1 Monitor(V)
0.00~100.00(%)
-
X
35
5
0h1523
V2 input display
V2 Monitor(V)
0.00~12.00(V)
0.00
O
37
0h1525
V2 input filter constant time
V2 Filter
0-10000(msec)
10
O
38
0h1526
V2 input minimum voltage
V2 Volt x1
0.00~10.00(V)
0.00
O
39
0h1527
Output % at V2 minimum voltage
V2 Perc y1
0.00~100.00(%)
0.00
O
40
0h1528
V2 input maximum voltage
V2 Volt x2
0.00~10.00(V)
10.00
O
41
0h1529
Output % at V2 maximum voltage
V2 Perc y2
0.00~100.00(%)
100.00
O
46
0h152E
Changing V2 rotation direction
V2 Inverting
0
No
0: No
O
1
Yes
47
0h152F
V2 quantizing level
V2 Quantizing
0.00
6
, 0.04~10.00(%)
0.04
O
50
7
0h1532
I2 input display
I2 Monitor(mA)
0~24(mA)
0
O
52
0h1534
I2 input filter constant time
I2 Filter
0-10000(msec)
10
O
53
0h1535
I2 input minimum current
I2 Curr x1
0.00~20.00(mA)
4.00
O
54
0h1536
Output % at I2 minimum current
I2 Perc y1
0.00~100.00(%)
0.00
O
55
0h1537
I2 input maximum current
I2 Curr x2
0.00~24.00(mA)
20.00
O
56
0h1538
Output % at I2 maximum current
I2 Perc y2
0.00~100.00(%)
100.00
O
61
0h153D
Changing I2 rotation direction
I2 Inverting
0
No
0: No
O
1
Yes
62
0h153E
I2 quantizing level
I2 Quantizing
0.00
8
, 0.04~10.00(%)
0.04
O
65
0h1541
P1 terminal function setting
P1 Define
0
None
1: Fx
Δ
1
Fx
66
0h1542
P2 terminal function setting
P2 Define
2
Rx
2: Rx
Δ
67
0h1543
P3 terminal function setting
P3 Define
3
RST
5: BX
Δ
68
0h1544
P4 terminal function setting
P4 Define
4
Disparo externo
3: RST
Δ
69
0h1545
P5 terminal function setting
P5 Define
5
BX
7: Sp-L
Δ
70
0h1546
P6 terminal function setting
P6 Define
6
JOG
8: Sp-M
Δ
71
0h1547
P7 terminal function setting
P7 Define
7
Speed-L
9: Sp-H
Δ
8
Speed-M
9
Speed-H
11
XCEL-L
12
XCEL-M
13
XCEL-H
14
XCEL Stop
15
RUN Enable
16
3-Wire
17
2nd Source
18
Exchange
1
IN-05’ setting range can be changed according to the ‘IN-06’ settings.
2
IN-12~IN-17codes appear whenIN-06 code is set as 1(Bipolar).
3
When set as 0,Quantizing is not available.
4
IN-20 code appears when analog voltage/current input terminal setting switch (SW3) is set as T1.
5
IN-35~IN47 codes appear when analog voltage/current input terminal setting switch (SW4) is set as V2
6
When set as 0,Quantizing is not available.
7
IN-50~IN-62 codes appear when analog voltage/current input terminal setting switch (SW5) is set as I2
8
When set as 0, Quantizing is not available.