36
_ LS ELECTRIC
Fan and Pump
H100
Application Function Group (PID)
Code Comm. No
Name
LCD Display
Set Range
Default
Attribute
*
17
0h1811
PID reference 2
auxiliary sourceselection
PID Ref2AuxSrc
3
V2
0: None
O
4
I2
6
Pulse
7
RS-485
8
FieldBus
10
EPID1 Output
11
EPID1 Fdb Val
12
1
V3
13
I3
18
0h1812
PID reference 2
auxiliary mode selection
PID Ref2AuxMod
0
M+(G*A)
0: M+(G*A)
O
1
M*(G*A)
2
M/(G*A)
3
M+(M*(G*A))
4
M+G*2*(A-50)
5
M*(G*2*(A-50))
6
M/(G*2*(A-50))
7
M+M*G*2*(A-50)
8
(M-A)^2
9
M^2+A^2
10
MAX(M, A)
11
MIN(M, A)
12
(M+A)/2
13
Root(M+A)
19
0h1813
PID reference 2 auxiliary gain
PID Ref2 Aux G
-200.0~200.0(%)
0.0
O
20
0h1814
PID feedback selection
PID Fdb Source
0
V1
0: V1
Δ
2
V2
3
I2
4
Int 485
5
FieldBus
7
Pulse
8
EPID1 Output
9
EPID1 Fdb Val
10
2
V3
11
I3
21
0h1815
PID feedback auxiliary source selection
1
PID Fdb Aux Src
0
None
0: None
Δ
1
V1
3
V2
4
I2
6
Pulse
7
Int 485
8
FieldBus
10
EPID1 Output
11
EPID1 Fdb Val
12
3
V3
13
I3
22
0h1816
PID feedback auxiliary mode selection
PID Fdb AuxMod
0
M+(G*A)
0: M+(G*A)
O
1
M*(G*A)
2
M/(G*A)
3
M+(M*(G*A))
4
M+G*2*(A-50)
5
M*(G*2*(A-50))
6
M/(G*2*(A-50))
7
M+M*G*2*(A-50)
8
(M-A)^2
9
M^2+A^2
10
MAX(M, A)
11
MIN(M, A)
12
(M+A)/2
13
Root(M+A)
1
‘12(V3)~13(I3)’ of PID-17 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.
2
‘10(V3)~11(I3)’ of PID-20 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.
3
'12(V3)~13(I3)’ of PID-21 are available when Extension IO option is equipped. Refer to Extension IO option manual for more detail information.