46
_ LS ELECTRIC
Fan and Pump
H100
Protective Function Group (PRT )
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
00
-
Jump code
Jump Code
1~99
40
O
05
0h1D05
I/O open phase protection
Phase Loss Chk
Bit
00~11
00
Δ
Bit 0
Fault trips other than LV trip
Bit 1
LV trip
06
0h1D06
Input open phase voltage band
IPO V Band
1~100(V)
15
O
07
0h1D07
Trip deceleration time
Trip Dec Time
0.0~600.0(sec)
3.0
0.75~90kW
O
90.0
110~500kW
08
0h1D08
Start upon trip reset
RST Restart
Bit
00~11
00
O
Bit 0
Fault trips other than LV trip
Bit 1
LV trip
09
0h1D09
Auto retry number
Retry Number
0~10
0
O
10
0h1D0A
Auto retry delay time
Retry Delay
0.0~600.0(sec)
5.0
O
11
0h1D0B
Operation when keypad
command islost
Lost KPD Mode
0
None
0: None
O
1
Warning
2
Free-Run
3
Dec
12
0h1D0C
Operation when speed
command is lost
Lost Cmd Mode
0
None
0: None
O
1
Free-Run
2
Dec
3
Hold Input
4
Hold Output
5
Lost Preset
13
1
0h1D0D
Time to decide lost speed command
Lost Cmd Time
0.1~120.0(sec)
1.0
O
14
0h1D0E
Operation frequency when speed commandis lost
Lost Preset F
0.00, Low Freq~High Freq
0.00
O
15
0h1D0F
Level to decide lost analog input
AI Lost Level
0
Half ofx1
0: Half of x1
O
1
Below x 1
17
0h1D11
Overload warning selection
OL Warn Select
0
No
0: No
O
1
Yes
18
0h1D12
Overload warning level
OL Warn Level
30~OL Trip Level(%)
110
O
19
0h1D13
Overload warning time
OL Warn Time
0.0~30.0(sec)
10.0
O
20
0h1D14
Operation at overload trip
OL Trip Select
0
None
1: Free-Run
O
1
Free-Run
2
Dec
21
0h1D15
Overload trip level
OL Trip Level
30~150(%)
120
O
22
0h1D16
Overload trip time
OL Trip Time
0.0~60.0(sec)
60.0
O
23
0h1D17
Under-load warning source selection
UL Source
0
Output Current
0: Output Current
Δ
1
Output Power
24
0h1D18
Under-load warning detection band
UL Band
0.0~100.0(%)
10.0
Δ
25
0h1D19
Under-load warning selection
UL Warn Sel
0
No
0: No
O
1
Yes
26
0h1D1A
Under-load warning time
UL Warn Time
0.0~600.0(sec)
10.0
O
27
0h1D1B
Under-load trip selection
UL Trip Sel
0
None
0: None
O
1
Free-Run
2
Dec
28
0h1D1C
Under-load trip time
UL Trip Time
0.0~600.0(sec)
30.0
O
31
0h1D1F
Operation at No Motor trip
No Motor Trip
0
None
0: None
O
1
Free-Run
32
0h1D20
No Motor trip
No Motor Level
1~100(%)
5
O
33
0h1D21
No Motor detection time
No Motor Time
0.1~10.0(sec)
3.0
O
34
0h1D22
Operation after detection by
overheat motor sensor
Thermal-T Sel
0
None
0 : None
O
1
Free-Run
2
Dec
35
0h1D23
Overheat motor sensor input selection
Thermal In Src
0
Thermal In
0: Thermal In
O
1
V2
36
0h1D24
Overheat motor sensor failure level
Thermal-T Lev
0.0~100.0(%)
50.0
O
1
PRT-13~PRT-15 codes appear when PRT-12 code is not set as 0: None.