48
_ LS ELECTRIC
Fan and Pump
H100
Protective Function Group (PRT )
Code Comm. No.
Name
LCD Display
Set Range
Default
Attribute
*
73
0h1D49
evel detection delay time
LDT Dly Time
0~9999(sec)
2
O
74
0h1D4A
Level detection reference value
LDT Level
Setting per source
Setting per source
O
75
0h1D4B
Level detection bandwidth
LDT Band width
Setting per source
Setting per source
O
76
0h1D4C
Level detection frequency
LDT Freq
0.00~High Freq(Hz)
20.00
O
77
0h1D4D
Level detection trip restart
LDT Restart DT
0.0~3000.0
60.0
79
0h1D4F
Cooling fan failure selection
FAN Trip Mode
0
Trip
0: Trip
O
1
Warning
80
0h1D50
Operation upon option trip
Opt Trip Mode
0
None
1: Free-Run
O
1
Free-Run
2
Dec
81
0h1D51
Low voltage delay time
LVT Delay
0.0~60.0(sec)
0.0
Δ
82
0h1D52
Selection of low voltage during operation
LV2 Trip Sel
0
No
1: No
Δ
1
Yes
83
0h1D53
CAP. life diagnosis current level
CAP. Diag Perc
10~100(%)
0
O
84
1
-
CAP. life diagnosis mode
CAP. Diag
0
None
0: None
Δ
1
Cap.Diag 1
2
Cap.Diag 2
3
Cap.Init
85
0h1D55
CAP. life diagnosis level 1
CAP. Level1
50.0~95.0(%)
0.0
Δ
86
2
0h1D56
CAP. life diagnosis level 2
CAP. Level2
-
0.0
X
87
0h1D57
Fan use accumulation %
Fan Time Perc
-
0
X
88
0h1D58
Fan exchange warning level
Fan Exchange
0.0~100.0(%)
0.0
O
90
0h1D5A
Battery low voltage selection
Low Battery
0
None
0: None
O
1
Warning
91
0h1D5B
Setting the function of Broken belt
Broken Belt Sel
0
None
0: None
Δ
1
Warning
2
Free-Run
92
0h1D5C
Operating the frequency of Broken belt
Broken Belt Freq
15.00~MaxFreq
15.00
Δ
93
0h1D5D
Motor torque current
Current Trq
-
-
X
94
0h1D5E
Torque current of operating Broken belt
Broken Belt Trq
0.0~100.0(%)
10.0
Δ
95
0h1D5F
Delay of operating Broken belt
Broken Belt Dly
0~600.0(sec)
10.0
Δ
1
PRT-84 is displayed when PRT-83 is set to more than ‘0(%)’. PRT- 84 can only be set in Auto-State.
2
PRT-86 is read only.