H100 _
47
Energy Saving Drive
Code Comm. No.
Name
LCD Display
Set Range
Default
Att ribute
*
37
0h1D25
Overheat motor sensor failure area
Thermal-T
0
Low
0: Low
O
1
High
38
1
0h1D26
Overheat motor detection sensor
ThermalMonitor
-
-
X
40
0h1D28
Overheat motor trip selection
ETH Trip Sel
0
None
0: None
1
Free-Run
O
2
Dec
41
0h1D29
Motor cooling fan type
Motor Cooling
0
Self-cool
0: Selfcool
O
1
Forced-cool
42
0h1D2A
Overheat prevention: 1 min. rating
ETH 1min
ETH Cont~150(%)
120
O
43
0h1D2B
Overheat prevention: continuous rating
ETH Cont
50~120(%)
100
O
44
0h1D2C
Fire Mode setting password
Fire Mode PW
0~9999
0
O
45
2
0h1D2D
Fire Mode setting
Fire Mode Sel
0
None
0: None
O
1
Fire Mode
2
Test Mode
46
3
0h1D2E
Fire Mode direction setting
Fire Mode Dir
0
Reverse
1: Forward
O
1
Forward
47
4
0h1D2F
Fire Mode speed setting
Fire Mode Freq
0~max Freq
60.00
O
48
0h1D30
Fire Mode operation count
Fire Mode Cnt
-
0
X
50
0h1D32
Stall prevention & flux breaking
Stall Prevent
Bit
0000~1111
0100
Δ
Bit 0
Accelerating
Bit 1
In constant speed
Bit 2
Decelerating
Bit 3
Flux Braking
51
0h1D33
Stall frequency 1
Stall Freq 1
Start frequency ~Stall frequency 2(Hz)
60.00
O
52
0h1D34
Stall level 1
Stall Level 1
30~150(%)
130
Δ
53
0h1D35
Stall frequency 2
Stall Freq 2
Start frequency 1 ~Stall frequency 3(Hz)
60.00
O
54
0h1D36
Stall level 2
Stall Level 2
30~150(%)
130
Δ
55
0h1D37
Stall frequency 3
Stall Freq 3
Start frequency2 ~Stall frequency 4(Hz)
60.00
O
56
0h1D38
Stall level 3
Stall Level 3
30~150(%)
130
Δ
57
0h1D39
Stall frequency 4
Stall Freq 4
Stall frequency 3~Max. frequency (Hz)
60.00
O
58
0h1D3A
Stall level 4
Stall Level 4
30~150(%)
130
Δ
59
0h1D3B
Flux Braking voltage gain
Flux Brake Kp
5.5~90kW
0~150(%)
0
O
110~500kW
0~10(%)
60
0h1D3C
Pipe broken detection setting
PipeBroken Sel
0
None
0: None
O
1
Warning
2
Free-Run
3
Dec
61
0h1D3D
Pipe broken detection level
PipeBroken Lev
0~100.0(%)
97.5
O
62
0h1D3E
Pipe broken detection time setting
PipeBroken DT
0.0~6000.0(Sec)
10.0
O
66
0h1D42
Damping resistance use rate
DB Warn %ED
0~30(%)
0
O
70
0h1D46
Level detection mode selection
LDT Sel
0
None
0 : None
O
1
Warning
2
Free-Run
3
Dec
71
0h1D47
Setting level detection mode
LDT Area Sel
0
Below Level
0: Below Level
O
1
Above Level
72
0h1D48
Level detection source
LDT Source
0
Output Current
0: Output Current
O
1
DC Link Voltage
2
Output Voltage
3
kW
4
HP
5
V1
6
V2
7
I2
8
PID Ref Value
9
PID Fdb Value
10
PID Output
11
EPID1 Fdb Val
12
EPID2 Fdb Val
1
PRT-38 code appears when PRT-34 code is not 0: None.
2
PRT-45 can only be set when PRT-44 is in Fire mode. To change the mode in PRT-44, create a new password for PRT-44.
3
PRT-46–47 are displayed when PRT-45 is not set to ‘0 (NONE)’
.
4
When Fire mode is set at PRT-45, PRT-46 is automatically set to forward, and the frequency set at PRT-47 cannot be edited. When PRT-45 is set to Test mode, PRT-46 and PRT-47 settings are editable.