Multi V 5
9. Setting the function
52
Installation of Outdoor Units
9.2 Dip Switch Setting
Select the mode/function/option/value using ‘►’, ‘
◀
’ Button and confirm that using the ‘
●
’ button after
dip switch No.5 is turned on.
• Functions “save in EEPROM” will be kept continuously, though the system power was reset.
• For detail information about SVC and IDU setting functions, refer to the installation manual or SVC manual.
Optional Mode Selection
Function Selection
Option Selection
Remarks
Content
Display
(
◎
)
Content
Display
(
◀
,
▶
◎
)
Default
Optional
(
◀
,
▶
◎
)
FDD
Fdd
Automatic Refrigerant Charging (Cooling)
Fd1
-
-
-
Automatic Refrigerant Charging (Heating)
Fd2
-
-
-
Refrigerant Amount Check (Cooling)
Fd3
-
-
-
Refrigerant Amount Check (Heating)
Fd4
-
-
-
Automatic
Fd7
-
-
-
All IDU operation (Cooling)
Fd8
-
-
Compulsory Operation
All IDU operation (Heating)
Fd9
-
-
for 1hour
Installa tion
Func
Cool & Heat Selector
Fn 1
oFF
oFF, oP1~oP2
save in EEPROM
High Static Pressure compensation
Fn 2
oFF
oFF, oP1~oP7
save in EEPROM
Night low noise
Fn 3
oFF
oFF, oP1~oP12
save in EEPROM
Overall Defrost
Fn 4
North America : oFF
Europe : oFF
Tropical : oN
on, oFF
save in EEPROM
ODU Addressing
Fn 5
0
0~255
save in EEPROM
Snow Removal & Rapid Defrost
Fn 6
oFF
oFF, oP1~oP3
save in EEPROM
Capacity Up Airflow Adjusting for IDU
(Heating)
Fn 7
oFF
on, oFF
save in EEPROM
Target Pressure Adjusting
Fn 8
oFF
oFF, oP1~oP6
save in EEPROM
Low Ambient Kit
Fn 9
oFF
on, oFF
save in EEPROM
High Efficiency Mode (Cooling Operation)
Fn 10
oFF
on, oFF
save in EEPROM
Auto Dust Removal Mode
Fn 11
oFF
oFF, oP1~oP5
save in EEPROM
Compressor Max. Frequency Limit
Fn 12
oFF
oFF, oP1~oP9
save in EEPROM
ODU Fan Max. RPM Limit
Fn 13
oFF
oFF, oP1~oP7
save in EEPROM
Smart Load Control
Fn 14
oFF
oFF, oP1~oP3
save in EEPROM
Humidity Reference
Fn 16
on
on, oFF
save in EEPROM
Compressor Input Current Limit
Fn 20
oFF
oFF, oP1~oP10
save in EEPROM
Optional Base panel Heater
Fn 23
oFF
on, oFF
save in EEPROM
Service
SvC
Vacuum mode
SE3
vACC
-
1time / 1 Selection
User
Idu
Comfort Cooling
Id10
EAch
-
save in EEPROM
SW01C (
: Confirm /
Automatic Addressing)
SW02C (
: backward)
SW04C (X : cancel)
DIP-SW01
7-Segment
SW01D (reset)
SW03C (
: forward)
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...