Multi V 5
7. Refrigerant piping system
24
Installation of Outdoor Units
7.2 Indoor Unit Connection
Indoor Unit connecting pipe from branch (a, b, c, d, e, f)
CAUTION
Indoor Unit capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
< 22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
≤
28.0(95,900)
Ø9.52(3/8)
Ø22.2(7/8)
• Bending radius should be at least twice the diameter of the pipe.
• Bend pipe after 500mm(19.7inch) or more from branch(or header).
Do not bend U type.
It may affect performance or result in noise.
If U type bending is required, the R should be more than 200mm
(7.9inch).
500mm[19.7inch]
or more
500mm[19.7inch]
or more