6. Electric Characteristics
89
Multi V 5
Outdoor Units
86 HP
50
380-415
Min.:342, Max.:456
172.7
190.0
200
41.3
81.7
98.0
7.20
10.0
88 HP
50
380-415
Min.:342, Max.:456
172.7
190.0
200
41.3
85.0
102.4
7.20
10.0
90 HP
50
380-415
Min.:342, Max.:456
190.0
209.0
200
45.6
84.0
101.6
7.20
10.0
92 HP
50
380-415
Min.:342, Max.:456
191.8
211.0
200
45.6
86.8
106.1
7.20
10.0
94 HP
50
380-415
Min.:342, Max.:456
192.7
212.0
200
45.6
91.1
109.5
7.20
10.0
96 HP
50
380-415
Min.:342, Max.:456
196.4
216.0
250
47.2
94.0
112.8
7.20
10.0
Model
Unit
Power Supply
COMP
OFM
Hz
Volts
Voltage-range
MCA
TOCA
MFA
MSC
RLA(Cooling)
RLA(Heating)
kW
FLA
Note
1. Voltage supplied to the unit terminals should be within the minimum and maximum
range.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MSC means the Max. current during the starting of compressor.
4. MSC and RLA are measured as the compressor only test condition.
5. OFM are measured as the outdoor unit test condition.
6. TOCA means the total over current value of each outdoor unit.
7. Select the wire size based on the larger value among MCA or TOCA.
8. MFA is recommended fuse amps.
9. TOCA is minimum required amperes for selecting the circuit breaker and ground fault
circuit interrupter. Please select the circuit breaker size equal or greater than TOCA.
All installation site must require attachment of an earth leakage breaker.[Circuit breaker
type is ELCB (Earth Leakage Circuit Breaker)].
10.Select the electrical equipment of combination unit according to the electrical
characteristics of individual unit.
’ : 2 unit combination models
Symbols
MCA :
Minimum Circuit Amperes (A)
TOCA :
Total Over Current Amperes (A)
MFA :
Maximum Fuse Amperes (A)
MSC :
Maximum Starting Current (A)
RLA :
Rated Load Amperes (A)
OFM :
Outdoor Fan Motor
kW :
Fan Motor rated output (kW)
FLA :
Full Load Amperes (A)
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...