10. Sound Levels
109
Multi V 5
Outdoor Units
10.2 Sound Power Levels
Note
• Data is valid at diffuse field condition
• Data is valid at nominal operating condition
• Sound level can be increased in static pressure mode or used air guide.
• Sound power level is measured on the rated condition in the semi-anechoic rooms.
• Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient)
of particular room in which the equipment in installed.
• Reference acoustic intensity 0dB = 10E-6μW/m
2
Model
Cooling
Heating
ARUM080LTE5
77.0
78.0
ARUM100LTE5
78.0
79.0
ARUM120LTE5
79.0
80.0
ARUM140LTE5
82.0
84.0
ARUM160LTE5
83.0
85.0
ARUM180LTE5
85.0
86.0
ARUM200LTE5
86.0
87.0
ARUM220LTE5
86.0
88.0
ARUM240LTE5
88.0
90.0
ARUM260LTE5
88.0
90.0
ARUM221LTE5
81.5
82.5
ARUM241LTE5
82.0
83.0
ARUM261LTE5
83.8
85.5
ARUM280LTE5
84.5
86.2
ARUM300LTE5
86.0
87.0
ARUM320LTE5
86.8
87.8
ARUM340LTE5
86.8
88.6
ARUM360LTE5
88.5
90.4
ARUM380LTE5
89.0
91.0
ARUM400LTE5
89.2
91.2
ARUM420LTE5
89.8
91.5
ARUM440LTE5
90.1
91.8
ARUM460LTE5
90.1
92.1
ARUM480LTE5
91.0
93.0
ARUM500LTE5
89.4
91.3
ARUM520LTE5
89.6
91.5
ARUM540LTE5
90.1
91.8
ARUM560LTE5
90.4
92.0
ARUM580LTE5
90.4
92.4
ARUM600LTE5
91.3
93.2
ARUM620LTE5
91.5
93.5
ARUM640LTE5
91.6
93.6
ARUM660LTE5
92.0
93.8
ARUM680LTE5
92.2
94.0
ARUM700LTE5
92.2
94.2
ARUM720LTE5
92.8
94.8
ARUM740LTE5
91.8
93.7
ARUM760LTE5
91.9
93.8
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...