9
Multi V 5
Installation of Outdoor Units
5. Installation
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit support block at the bottom shall have width of at least 100mm(3-15/16inch) under the units
legs before being fixed.
• The outdoor unit support block hould have minimum height of 200mm(7-7/8inch).
• Anchor bolts must be inserted at least 75mm(2-15/16inch).
5.1 The location of the Anchor bolts
Chassis
A [mm(inch)]
B [mm(inch)]
UXA
930(36-5/8)
730(28-3/4)
UXB
1,240(48-13/16)
1,040(40-15/16)
At least 100mm
At least 100mm
At least 100mm
At least 100mm
At least 100mm
At least 100mm
Outdoor units
should not be
supported only by
the corner supports.
Center of the Unit
Center of the Unit
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
(3-15/16 inch)
7
31(28-25/32)
7
60(29-29/32)
65
(2-9/16)
65
(2-9/16)
Unit : mm(inch)
At
least
65(2-9/16)
At
least
65(2-9/16)