8. Capacity Correction Factor
672
Multi V 5
Outdoor Units
Note
1. These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load under
standard conditions.(Moreover, under partial load conditions there is only a minor deviation from the rate of
change in capacity shown in the above figures.)
2. With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant
control when heating is carried out.
3. If heat insulation of piping is insufficient, heat loss will become larger and capacity will decrease.
4. Method of calculating cooling / heating capacity : maximum cooling / heating capacity of outside units = cooling
/ heating capacity of outside units obtained from capacity table X capacity correction factor due to piping length
to the farthest indoor unit
5. Equivalent piping length for Y Branch and other pipes can be calculated with following table.
6. When the any one (or both ) of below conditions are satisfied, the diameter of main pipe must be increased.
• The equivalent length between outdoor unit and the farthest indoor unit is 90m or more (Liquid or Gas pipes
are increased in accordance with below table)
• The level difference (Outdoor unit
˩
Indoor unit) is 50m or more (Only liquid pipe is increased)
Refer to the table (Refrigerant pipe diameter from outdoor unit to first branch.) in the 'installation of outdoor units'
part.
7. Read cooling / heating capacity rate of change in the above figures based on the following equivalent length. :
overall equivalent length = (equivalent length of main pipe) X correction (equivalent length after first
branching)
•
8, 10, 12, 14, 16, 18, 20, 22, 24, 26, 28, 30, 32, 34HP
•
36, 38, 40, 42, 44, 46, 48, 50, 52, 54, 56, 58, 60HP
•
62, 64, 66, 68, 70, 72, 74, 76, 78, 80, 82, 84, 86, 88, 90, 92, 94, 96HP
mm
(inch)
Ø6.35
(1/4)
Ø9.52
(3/8)
Ø12.7
(1/2)
Ø15.88
(5/8)
Ø19.05
(3/4)
Ø22.2
(7/8)
Ø25.4
(1)
Ø28.58
(1-1/8)
Ø31.8
(1-1/4)
Ø34.9
(1-3/8)
Ø38.1
(1-1/2)
Ø41.3
(1-5/8)
Ø44.5
(1-3/4)
Ø53.98
(2-1/8)
Elbow (m)
0.16
0.18
0.2
0.25
0.35
0.4
0.45
0.5
0.55
0.6
0.65
0.7
0.75
0.85
Y Branch (m)
0.5
Header (m)
1
HR Unit (m)
2.5
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
0.5
Heating(Liquid pipe)
1
0.2
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
0.5
Heating(Liquid pipe)
1
0.4
Rate of change
(object piping)
Correction factor
standard size
size increase
Cooling(Gas pipe)
1
-
Heating(Liquid pipe)
1
0.4
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...