Multi V 5
2. Control System List
14
Control System
Outline of system
Return
Air
Tempera
- ture
Control
•
LG Control : Fixed T
e
+ T
r
or T
Room
A fixed evaporating or condensing temperature of a DX coil (T
e
) can be controlled by either return air temperature (T
r
) or room air
temperature (T
Room
).
A fixed target evaporating or condensing temperature can be changed in MULTI V and Single outdoor unit setting.
•
DDC Control by Contact Signal : Fixed T
e
+ T
r
or T
Room
The DDC controls return air temperature (T
r
) or room air temperature (T
Room
) by transferring AI / DI / DO signal to the AHU
Communication Kit for Return air control.
A fixed target evaporator or condensing temperature (T
e
) can be changed in MULTI V and Single outdoor setting.
LG wired remote controller and LG Central Controller can be optionally applied, but only monitoring function is possible.
• If you need more detail, please refer to the Control PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON))
DX
Coil
AHU
Room
AHU Controller
PAHCMR000
Outdoor Unit
LG Central
Controller
(Optional)
Remote
Controller
T
T
r
e
T
Room
.
DX
Coil
AHU
Room
PAHCMR000
AHU Controller
Outdoor Unit
DDC
(Field Supply)
Remote
Controller
(Monitoring)
.
AI / DI / DO
Signal
LG Central
Controller
(Monitoring only)
T
T
r
e
T
Room
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...