7. Refrigerant piping system
17
Multi V 5
Installation of Outdoor Units
■
Y branch, Header and HR unit connection pattern
Note
• If the large capacity(76kBtu/h and 96kBtu/h unit) indoor units are installed, two neighboring outlets of one HR
unit are linked by Y branch pipe and connected to one indoor unit.
Pattern 1
HR1
48k
48k
1
2
HR2
48k
48k
3
4
B
• Impossible installation : Head branch pipe HR unit
Pattern 2
HR1
1
2
3
4
5
6
7
7k
7k
7k
7k
7k
24k
24k
• Impossible installation : HR unit Head branch
pipe Y and Head branch pipe.
B
A
Pattern 3
HR1
54k
54k
54k
54k
1
2
3
4
• The maximum total capacity of indoor
units is 67.4kW(230 kBtu/h).
Pattern 4
15k 15k 15k 15k
1
2
3
4
• The maximum total capacity of a branch
pipe of HR unit is 17.5kW(60 kBtu/h).
HR1
B
Pattern 5
HR1
48k
48k
A
1
2
HR2
48k
48k
3
4
HR1
[
Y
[
Y
[
Y
XY
XY
B
Pattern 6
A
A
A
1
2
3
4
5