8. Capacity Correction Factor
674
Multi V 5
Outdoor Units
8.5 Defrosting Correction Factor for Heating Operation
The capacity table does not consider reduction in capacity when frost has accumulated or during defrosting.
The capacity values considered these factors, in other words the integrated heating capacity values, can be
obtained as follows:
[ Formula ]
• Integrated Heating capacity = A
• Value given in table of capacity characteristics = B
• Integrated correction factor for frost accumulation = C
• A=B x C
[ Correction factor for finding integrated Heating capacity ]
Normal Defrost Operation
Partial Defrost Operation
Please note that there will be temporary reduction in capacity when snow piles up on the outside surface
of the outdoor unit heat exchanger. Of course, it will be different in degree depending on a number of other
factors, for example, the outdoor temperature(°CDB), the relative humidity(RH) and the frosting amount.
Inlet Port Temperature of Heat Exchange (
,RH 85%)
-7
-5
-
3
0
3
5
7
Integrated Correction Factor for Frost Accumulation
(Normal Defrost Operation)
0.92 0.90 0.86 0.84 0.85 0.90
1.0
Integrated Correction Factor for Frost Accumulation
(Partial Defrost Operation)
0.92 0.90 0.86 0.90 0.93 0.95
1.0
Integrated Correction Factor for Frost Accumulation
(Normal Defrost Operation / Dual sensing )
0.92 0.90 0.86 0.86 0.86 0.91
1.0
Integrated Correction Factor for Frost Accumulation
(Partial Defrost Operation / Dual sensing )
0.92 0.90 0.86 0.91 0.94 0.95
1.0
Normal Defrost
Operation
Normal Defrost
Operation
Time
Heating
Operation
Heating
Capacity
1 Cycle
Time
Heating
Capacity
1 Cycle
Normal Defrost
Operation
Normal Defrost
Operation
Heating Operation
Partial Defrost Operation
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...