2. Control System List
5
Multi V 5
Control System
Category
Controller
name
Model name
Compatible
Product
Dimensions
(W x H x D, mm)
Feature
Central
controller
AC Manager 5
PACM5A000
All IDU
ERV
1)
ERV DX
Heating
AHU
Chiller*
270 x 155 x 65
• PC Access Controller
• DC 12 V Adaptor
• Max 8,192 indoor unit control
(Supports 32 ACP IV or AC Smart IV)
• Chrome(Recommended), Safari,
Internet Explorer 11 support
AC Manager IV
PACM4B000
All IDU
ERV
1)
ERV DX
Heating
AHU
Chiller*
-
• PC installation SW
• Max 8,192 indoor unit control
(Supports 32 ACP IV or AC Smart IV)
• Windows XP/7/8/8.1/10 OS support
ACP 5
PACP5A000
All IDU
ERV
1)
ERV DX
Heating
AHU
Chiller*
270 x 155 x 65
• PC Access Controller
• DC 12 V Adaptor
• Max 256 indoor unit control
• RS-485 : 6 channels
CH1~4 : indoor unit
2)
CH5 : LGAP(AHU) or Modbus(AHU,
Chiller, ACS I/O)
CH6 : Modbus(AHU, Chiller, ACS I/O)
• DI 10EA, DO 4EA
(DI1 : Emergency stop Only)
ACP IV
PACP4B000
ACP BACnet
PQNFB17C0
All IDU
ERV
1)
ERV DX
Heating
AHU
270 x 155 x 65
• PC Access Controller
• Max 256 indoor unit control
• DC 12 V Adaptor
• RS-485 : 6 channels
CH1~4 : indoor unit
2)
CH5 : LGAP(AHU)
CH6 : Modbus(AHU, Chiller, ACS I/O)
• DI 10EA, DO 4EA
(DI1 : Emergency stop Only)
• BACnet IP Protocol Support
• Modbus TCP Protocol Support
• BTL Certified(B-ASC)
ACP Lonworks
PLNWKB000
All IDU
ERV
1)
ERV DX
Heating
AHU
270 x 155 x 65
• PC Access Controller
• Max 64 indoor unit control
• DC 12 V Adaptor
• RS-485 : 6 channels
Lon Comm. : 1 channel
CH1~4 : indoor unit
2)
CH5 : LGAP(AHU)
CH6 : Not use
LON : Lon Talk
• Lonworks Protocol Support
• 1) ERV : Energy Recovery Ventilation
• 2) Indoor unit : IDU, ERV, DX ERV, Heating, DO Kit
• * It needs to apply Chiller Option KIT.
• If you need more detail, please refer to the Control PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON))
Summary of Contents for ARUM080LTE5
Page 1: ...Heat Recovery Heat Pump R410A 50Hz 60Hz 0CVV0 01E Replaces 0CVV0 01D P No MFL67474071 ...
Page 85: ...78 Multi V 5 Outdoor Units 4 Wiring Diagrams 4 1 8 10 12 HP UXA 1 Comp ...
Page 86: ...4 Wiring Diagrams 79 Multi V 5 Outdoor Units 4 2 14 16 HP UXB 1 Comp ...
Page 87: ...Multi V 5 4 Wiring Diagrams 80 Outdoor Units 4 3 18 20 22 24 26HP UXB 2 Comp ...
Page 766: ...Special Guide Multi V 5 1 Cautions for Refrigerant Leaks 2 Guide for installing at seaside ...