Design and installation
3. Installation Space
3.1 Clearance around outdoor units
• Ensure that the space around the back is
or more more than 300 mm on the
opposite to the PCB side and secure 600
mm space near the compressor and PCB
side of the air conditioner for service.
• Install the unit so that its discharge port
faces to the wall of the building. Keep a
distance 500mm or more between the unit
and the wall surface.
• Supposing the wind direction during the
operation season of the air conditioner,
install the unit so that the discharge port is
set at right angle to the wind direction.
300 mm or more
300 mm or more
300 mm
or more
Sunroof
Fence or
obstacles
600 mm or more
(Service space)
100 mm
100 mm
or more
or more
300 mm
or more
700 mm
or more
Outdoor unit is representative. Actual appearance of outdoor unit
may be different but clearances will stay the same.
Air inlet grille
500
Blown
air
Strong
wind
Strong
wind
Turn the air outlet side toward the build-
ing's wall, fence or windbreak screen.
Set the outlet side at a right angle
to the direction of the wind.
Outdoor unit is representative. Actual appearance of outdoor unit may be
different but clearances will stay the same.
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...