6. Performance Data
29
THERMA V
Split Type
Outdoor unit
̰
AHUW168A3 [HU163 U33] + AHNW16809A3 [HN1639 NK3]
Peak Capacity (Not included defrost effect)
Total Capacity (Included defrost effect)
Note
1. DB : Dry bulb temperature(
), LWT : Leaving water temperature(
)
2. TC : Total capacity(kW), PI : Power Input(kW)
3. PC : Peak Capacity (Not included defrost effect, kW)
4. Direct interpolation is permissible. Do not extrapolate.
5. Measuring procedure follows EN-14511.
• Rated values are based on standard conditions, and it can be found on specifications.
• Above table values may not be matched according to installation condition. Except for rated value, the performance is not guaranteed.
• In accordance with the test standard(or nations), the rating will vary slightly.
Outdoor
Temperature
LWT 30
LWT 35
LWT 40
LWT 45
LWT 50
LWT 55
PC
PI
PC
PI
PC
PI
PC
PI
PC
PI
PC
PI
-20
DB
13.45
4.53
12.76
4.91
12.06
5.30
11.36
5.69
-
-
-
-
-15
DB
14.04
4.36
13.31
4.73
12.58
5.10
11.86
5.48
11.13
5.85
-
-
-7
DB
14.98
4.09
14.20
4.44
13.42
4.79
12.65
5.14
11.87
5.49
11.09
5.84
-4
DB
15.33
3.99
14.53
4.33
13.74
4.67
12.94
5.01
12.15
5.36
11.35
5.69
-2
DB
15.56
3.92
14.76
4.25
13.95
4.59
13.14
5.04
12.33
5.39
11.53
5.65
2
DB
16.03
3.78
15.20
4.12
14.37
4.64
13.54
5.10
12.71
5.46
11.88
5.72
7
DB
16.88
3.46
16.00
3.76
15.13
4.05
14.25
4.41
13.38
4.72
12.50
4.94
10
DB
17.38
3.26
16.48
3.54
15.58
3.82
14.68
4.10
13.78
4.38
12.88
4.66
15
DB
18.23
2.94
17.28
3.19
16.34
3.44
15.39
3.70
14.45
3.95
13.50
4.20
18
DB
18.73
2.75
17.76
2.98
16.79
3.22
15.82
3.45
14.85
3.69
13.88
3.92
Outdoor
Temperature
LWT 30
LWT 35
LWT 40
LWT 45
LWT 50
LWT 55
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-20
DB
12.79
4.44
12.13
4.82
11.61
5.23
11.08
5.64
-
-
-
-
-15
DB
13.35
4.28
12.65
4.64
12.12
5.03
11.56
5.43
10.99
5.82
-
-
-7
DB
14.24
4.01
13.50
4.35
12.93
4.72
12.34
5.09
11.72
5.46
11.09
5.84
-4
DB
13.73
3.71
13.02
4.03
12.67
4.43
12.27
4.84
11.83
5.26
11.35
5.69
-2
DB
13.37
3.52
12.68
3.82
12.48
4.24
12.22
4.78
11.89
5.25
11.53
5.65
2
DB
12.60
3.15
11.95
3.41
12.07
4.07
12.09
4.69
12.03
5.24
11.88
5.72
7
DB
16.88
3.46
16.00
3.76
15.13
4.05
14.25
4.41
13.38
4.72
12.50
4.94
10
DB
17.38
3.26
16.48
3.54
15.58
3.82
14.68
4.10
13.78
4.38
12.88
4.66
15
DB
18.23
2.94
17.28
3.19
16.34
3.44
15.39
3.70
14.45
3.95
13.50
4.20
18
DB
18.73
2.75
17.76
2.98
16.79
3.22
15.82
3.45
14.85
3.69
13.88
3.92
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...