2. Specifications
9
THERMA V
Split Type
Outdoor unit
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation.
4. Performances are based on the following conditions :
• Cooling : Inlet/Outlet Water Temp. 23°C/18°C, Outdoor Air Temp. 35°CDB / 24°CWB
• Heating : Inlet/Outlet Water Temp. 30°C/35°C, Outdoor Air Temp. 7°CDB / 6°CWB
• Interconnected Pipe Length is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is Zero.
5. This product contains Fluorinated greenhouse gases.
6. Sound Performances are based on the following conditions.
• Sound Power Level : Measured according to EN14825.
• Sound Pressure Level : Calculated value according to distance of sound power.
Outdoor Units
AHUW146A3 [HU141 U33]
AHUW166A3 [HU161 U33]
Power Supply
V, Ø, Hz
220-240 / 1 / 50
220-240 / 1 / 50
Operation Range
(Outdoor Tempera-
ture)
Cooling
Min. ~ Max.
°C DB
5 ~ 48
5 ~ 48
Heating
Min. ~ Max.
°C DB
-20 ~ 35
-20 ~ 35
Domestic Hot
Water
Min. ~ Max.
°C DB
-
-
Compressor
Type
-
Hermetic Motor
Hermetic Motor
Model
Model x No.
GPT442MAA x 1
GPT442MAA x 1
Diplacement
cm³/Rev.
44.2
44.2
Capacity
kW
13.92
13.92
Motor Type
-
BLDC
BLDC
Motor Output
Rated
W x No.
4,000 x 1
4,000 x 1
Refrigerant
Type
-
R410A
R410A
GWP
(Global Warming Potential)
-
2,087.5
2,087.5
Precharged Amount
g
2,300
2,300
t-CO2 eq.
-
4.80
4.80
Chargeless-Pipe Length
m
7.5
7.5
Additional Charging Volume
g/m
40
40
Control
-
Electronic Expansion Valve
Electronic Expansion Valve
Refrigerant Oil
Type
-
FVC68D
FVC68D
Charged Volume
cc x No.
1,300 x 1
1,300 x 1
Heat Exchanger
Quantity
EA
2
2
Specification
s
Row
EA
2
2
Column
EA
32
32
Fins per Inch
EA
14
14
Fan
Type
-
Propeller
Propeller
Air Flow Rate
Rated
m³/min x No.
55 x 2
55 x 2
Fan Motor
Type
-
BLDC
BLDC
Output
W x No.
124 x 2
124 x 2
Sound Power Level
Heating
Rated
dB(A)
66
66
Piping Connections
Liquid
Type
-
Flare
Flare
Outer Dia.
mm(inch)
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Gas
Type
-
Flare
Flare
Outer Dia.
mm(inch)
Ø 15.88 (5/8)
Ø 15.88 (5/8)
Piping Length
Standard
m
7.5
7.5
Max.
m
50
50
Piping Level Difference Outdoor Unit
~ Indoor Unit
Max.
m
30
30
Dimensions
Unit
W x H x D
mm
950 x 1,380 x 330
950 x 1,380 x 330
Packed Unit
W x H x D
mm
1,140 x 1,462 x 461
1,140 x 1,462 x 461
Weight
Unit
kg
94.0
94.0
Packed Unit
kg
107.0
107.0
Wiring Connections
Power Supply Cable
(Included Earth)
No. x mm²
3 x 6.0 (H07RN-F)
3 x 6.0 (H07RN-F)
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...