THERMA V
Split Type
6. Performance Data
20
Outdoor unit
6.1.2 Combination with DHW tank Integrated type
̰
AHUW096A3 [HU091 U43] + AHNW16606B0 [HN1616T NB0]
̰
AHUW126A3 [HU121 U33] + AHNW16606B0 [HN1616T NB0]
̰
AHUW146A3 [HU141 U33] + AHNW16606B0 [HN1616T NB0]
̰
AHUW166A3 [HU161 U33] + AHNW16606B0 [HN1616T NB0]
̰
AHUW128A3 [HU123 U33] + AHNW16606B0 [HN1616T NB0]
Note
1. DB : Dry bulb temperature(
), LWT : Leaving water temperature(
)
2. TC : Total capacity(kW), PI : Power Input(kW)
3. Direct interpolation is permissible. Do not extrapolate.
4. Measuring procedure follows EN-14511.
• Rated values are based on standard conditions, and it can be found on specifications.
• Above table values may not be matched according to installation condition. Except for rated value, the performance is not guaranteed.
• In accordance with the test standard(or nations), the rating will vary slightly.
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
7.30
2.51
8.09
2.54
8.89
2.57
9.42
2.59
10.21
2.61
10.75
2.63
-
-
30
DB
6.72
2.68
7.45
2.71
8.18
2.74
8.67
2.76
9.40
2.79
9.89
2.81
-
-
35
DB
6.43
2.76
7.13
2.79
7.83
2.83
8.30
2.85
9.00
2.88
9.47
2.90
9.94
2.92
40
DB
6.14
2.85
6.81
2.88
7.48
2.91
7.93
2.94
8.60
2.97
9.04
2.99
9.49
3.01
45
DB
5.85
2.93
6.49
2.97
7.13
3.00
7.55
3.02
8.19
3.06
8.62
3.08
9.04
3.10
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
7.03
2.41
8.06
2.43
9.10
2.45
9.79
2.47
10.82
2.49
11.51
2.50
-
-
30
DB
6.85
2.93
7.85
2.96
8.86
2.99
9.53
3.00
10.54
3.03
11.21
3.05
-
-
35
DB
6.75
3.20
7.75
3.22
8.74
3.25
9.41
3.27
10.40
3.30
11.06
3.32
11.73
3.34
40
DB
6.66
3.46
7.64
3.49
8.62
3.52
9.28
3.54
10.26
3.57
10.91
3.59
11.57
3.61
45
DB
6.57
3.72
7.54
3.75
8.50
3.79
9.15
3.81
10.12
3.84
10.76
3.86
11.41
3.89
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
7.43
2.58
8.53
2.60
9.62
2.62
10.35
2.64
11.45
2.66
12.18
2.68
-
-
30
DB
7.24
3.14
8.31
3.17
9.37
3.19
10.08
3.21
11.15
3.24
11.86
3.26
-
-
35
DB
7.14
3.42
8.19
3.45
9.25
3.48
9.95
3.50
11.00
3.53
11.70
3.55
12.40
3.57
40
DB
7.05
3.70
8.08
3.73
9.12
3.77
9.81
3.79
10.85
3.82
11.54
3.84
12.23
3.86
45
DB
6.95
3.98
7.97
4.02
8.99
4.05
9.68
4.07
10.70
4.11
11.38
4.13
12.06
4.16
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
8.11
2.92
9.30
2.95
10.50
2.97
11.30
2.99
12.49
3.02
13.29
3.03
-
-
30
DB
7.90
3.56
9.06
3.59
10.22
3.62
11.00
3.64
12.16
3.67
12.94
3.69
-
-
35
DB
7.79
3.87
8.94
3.91
10.09
3.94
10.85
3.97
12.00
4.00
12.77
4.02
13.53
4.05
40
DB
7.69
4.19
8.82
4.23
9.95
4.27
10.70
4.29
11.84
4.33
12.59
4.35
13.35
4.38
45
DB
7.58
4.51
8.70
4.55
9.81
4.59
10.56
4.62
11.67
4.66
12.42
4.68
13.16
4.71
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
7.03
2.41
8.06
2.43
9.10
2.45
9.79
2.47
10.82
2.49
11.51
2.50
-
-
30
DB
6.85
2.93
7.85
2.96
8.86
2.99
9.53
3.00
10.54
3.03
11.21
3.05
-
-
35
DB
6.75
3.20
7.75
3.22
8.74
3.25
9.41
3.27
10.40
3.30
11.06
3.32
11.73
3.34
40
DB
6.66
3.46
7.64
3.49
8.62
3.52
9.28
3.54
10.26
3.57
10.91
3.59
11.57
3.61
45
DB
6.57
3.72
7.54
3.75
8.50
3.79
9.15
3.81
10.12
3.84
10.76
3.86
11.41
3.89
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...