6. Performance Data
19
THERMA V
Split Type
Outdoor unit
̰
AHUW166A3 [HU161 U33] + AHNW16606A3 [HN1616 NK3]
̰
AHUW128A3 [HU123 U33] + AHNW16809A3 [HN1639 NK3]
̰
AHUW148A3 [HU143 U33] + AHNW16809A3 [HN1639 NK3]
̰
AHUW168A3 [HU163 U33] + AHNW16809A3 [HN1639 NK3]
Note
1. DB : Dry bulb temperature(
), LWT : Leaving water temperature(
)
2. TC : Total capacity(kW), PI : Power Input(kW)
3. Direct interpolation is permissible. Do not extrapolate.
4. Measuring procedure follows EN-14511.
• Rated values are based on standard conditions, and it can be found on specifications.
• Above table values may not be matched according to installation condition. Except for rated value, the performance is not guaranteed.
• In accordance with the test standard(or nations), the rating will vary slightly.
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
8.54
1.97
10.69
2.36
11.89
2.52
12.91
2.68
13.98
2.85
14.97
3.01
-
-
30
DB
9.70
3.07
11.31
3.47
12.22
3.75
13.34
3.60
13.63
3.55
14.21
3.50
-
-
35
DB
8.92
3.30
10.82
3.81
11.66
3.88
12.63
3.91
13.00
3.60
13.43
3.85
13.96
3.98
40
DB
8.51
3.67
10.03
4.19
11.02
4.31
11.70
4.36
11.93
3.97
12.37
4.05
12.85
4.13
45
DB
7.52
3.54
8.85
4.47
9.73
4.55
10.55
4.62
11.42
4.69
11.80
4.64
12.16
4.58
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
7.60
1.59
8.55
1.70
9.51
1.82
10.33
1.94
11.19
2.05
11.98
2.17
-
-
30
DB
8.62
2.46
9.05
2.50
9.78
2.71
10.67
2.60
10.90
2.57
11.37
2.53
-
-
35
DB
7.94
2.66
8.66
2.75
9.33
2.80
10.10
2.82
10.40
2.60
10.75
2.78
11.16
2.88
40
DB
7.56
2.96
8.02
3.03
8.81
3.12
9.36
3.16
9.54
2.87
9.89
2.93
10.28
2.99
45
DB
6.38
3.17
7.08
3.22
7.79
3.28
8.44
3.33
9.14
3.39
9.44
3.34
9.73
3.30
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
8.13
1.80
9.87
2.02
10.97
2.16
11.92
2.29
12.91
2.44
13.82
2.57
-
-
30
DB
9.24
2.81
10.44
2.97
11.29
3.21
12.31
3.08
12.58
3.04
13.12
2.99
-
-
35
DB
8.50
3.03
9.99
3.25
10.76
3.32
11.65
3.35
12.00
3.08
12.40
3.29
12.88
3.41
40
DB
8.10
3.37
9.25
3.59
10.17
3.69
10.80
3.73
11.01
3.40
11.42
3.47
11.86
3.53
45
DB
7.17
3.25
8.17
3.82
8.99
3.89
9.73
3.95
10.55
4.02
10.89
3.96
11.23
3.91
Outdoor
Temperature
LWT 7°C
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20
DB
8.54
1.97
10.69
2.36
11.89
2.52
12.91
2.68
13.98
2.85
14.97
3.01
-
-
30
DB
9.70
3.07
11.31
3.47
12.22
3.75
13.34
3.60
13.63
3.55
14.21
3.50
-
-
35
DB
8.92
3.30
10.82
3.81
11.66
3.88
12.63
3.91
13.00
3.60
13.43
3.85
13.96
3.98
40
DB
8.51
3.67
10.03
4.19
11.02
4.31
11.70
4.36
11.93
3.97
12.37
4.05
12.85
4.13
45
DB
7.52
3.54
8.85
4.47
9.73
4.55
10.55
4.62
11.42
4.69
11.80
4.64
12.16
4.58
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...