12
THERMA V
Split Type
Hydro Box Unit
6. Hydraulic Performance
6.1 Water Pump Capacity
̰
Water volume and pump capacity
The water pump is BLDC, so it may be required to change default water pump speed in case of noise by waterflow.
In most case, however, it is strongly recommended to set speed as Maximum.
Notice
Water pump speed : To secure enough water flow rate, do not set water pump speed as "Min."
It can lead unexpected flow rate error CH14.
AHNW16606A3, AHNW16809A3
Performance test based on standard ISO 9906 with pre-pressure 2.0bar and liquid temperature 20°C.
WARNING
Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
0 10 20 30 40 50 60 70 80 90 100
MAX. (RPM)
3500
3000
2500
2000
1500
1000
Min. flow
Total Head, Ht (m)
Pumping Capacity, Q (ℓ/min)
Pump model : PY-122NDDD3