THERMA V
Split Type
4. Water Control
6
Design and installation
4.3 Capacity correction factor by antifreeze
Correction factor of cooling capacity
Correction factor of heating capacity
Antifreeze Type
Item
Antifreeze % by wt
10%
20%
30%
40%
50%
Methanol
Cooling
0.998
0.997
0.995
0.993
0.992
Heating
0.995
0.990
0.985
0.979
0.974
Pressure Drop
1.023
1.057
1.091
1.122
1.160
Ethylene glycol
Cooling
0.996
0.991
0.987
0.983
0.979
Heating
0.993
0.985
0.977
0.969
0.961
Pressure Drop
1.024
1.068
1.124
1.188
1.263
Propylene glycol
Cooling
0.993
0.987
0.980
0.974
0.968
Heating
0.966
0.973
0.960
0.948
0.935
Pressure Drop
1.040
1.098
1.174
1.273
1.405
Co
rrectio
n
Fa
cto
r
0%
10%
20%
30%
40%
50%
1.000
0.990
0.980
0.970
Antifreeze % by wt
0.960
0.950
0.940
0.930
Methanol
Ethylene glycol
Prlpylene glycol
Co
rrectio
n
Fa
cto
r
0%
10%
20%
30%
40%
50%
1.000
0.990
0.980
Antifreeze % by wt
0.970
0.960
0.950
0.940
0.930
Methanol
Ethylene glycol
Prlpylene glycol
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...