1. Alternative Refrigerant R410A
• The refrigerant R410A has the property of higher operating pressure in comparison with R22.
Therefore, all materials have the characteristics of higher resisting pressure than R22 ones and this
characteristic should be also considered during the installation.R410A is an azeotrope of R32 and R125 mixed
at 50:50, so the ozone depletion potential (ODP) of R410A is 0.
CAUTION
•
The wall thickness of the piping should comply with the relevant local and national regulations for the
designed pressure 3.8MPa
•
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work
properly.
•
Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
•
For high-pressure refrigerant, any unapproved pipe must not be used.
•
Do not heat pipes more than necessary to prevent them from softening.
•
Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with
R22.
Summary of Contents for 5BPU0-02C
Page 1: ...Air to Water Heat Pump Split Type R410A 50Hz 5BPU0 02D Replaces 5BPU0 02C P No MFL66101112 ...
Page 3: ...General Information THERMA V Split Type 1 Model Line Up 2 Nomenclature ...
Page 9: ...Indoor Unit THERMA V Split Type Hydro Box Unit DHW Tank Integrated Unit ...
Page 17: ...8 THERMA V Split Type Hydro Box Unit 4 Wiring Diagrams AHNW16606A3 HN1616 NK3 ...
Page 18: ...4 Wiring Diagrams 9 THERMA V Split Type Hydro Box Unit AHNW16809A3 HN1639 NK3 ...
Page 31: ...THERMA V Split Type 4 Wiring diagrams 8 DHW Tank Integrated Unit Indoor unit Controller ...