Technical data
Leuze electronic
RSL 410
89
Table 15.8:
Inputs
Table 15.9:
Safety-related switching outputs
Table 15.10:
Inputs and outputs
Reset
+24 V, dynamically monitored (0.12 s to 4 s)
Signal definition:
High/logical 1
16 - 30 V
Low/logical 0
< 3 V
OSSD transistor safety-related switching outputs
2 safe PNP semiconductor outputs
Short-circuit proof, cross circuit monitored
Minimum
Typical
Maximum
Response time
80 ms
(2 scans)
1000 ms
(25 scans)
Switching voltage high active
U
B
– 3.2 V
Switching voltage low
2.0 V
Switching current
300 mA
Cut-off frequency f
g
1 kHz
Load capacity C
load
100 nF
Cable length between safety sensor and load with
cross section 0.25 mm
2
25 m
Permitted wire cross section
0.25 mm
2
Test pulse width
60 µs
110 µs
Test pulse distance
35 ms
40 ms
40 ms
The safety-related transistor outputs perform the spark extinction. With transistor outputs, it is
therefore neither necessary nor permitted to use the spark extinction circuits recommended by
contactor or valve manufacturers (RC elements, varistors or recovery diodes), since these con
-
siderably extend the decay times of inductive switching elements.
Features
Max. output cur
-
rent I
a
Min. input cur
-
rent I
e
Typical connection
components
EX/A=changeover-capable
(EA1)
20 mA
(-20 mA)
10 mA
(-10 mA)
Auxiliary contact of
power contactor
(EDM)
AX=output
Current limited, short-circuit proof
(A1, MELD)
100 mA
(-20 mA)
---
Lamp (PNP only)
Control input (PNP/
NPN)
Signal definition:
High/logical 1
16 - 30 V
Low/logical 0
< 3 V