Starting up the device
Leuze electronic
RSL 410
73
Shutting down safety sensor and removing from machine
When you shut down the safety sensor and store it away for a later use, you must reset the safety sensor
to the factory settings.
Reset the safety sensor to the factory settings using the software.
In the device manager (DTM) of the safety sensor, select the
CONFIGURATION
tab. Click the [Reset
safety configuration] button.
10.5 Restarting
Restarting the machine with the safety sensor
If you have only shut down the system with the safety sensor temporarily and are restarting the system
without any changes, you can restart the safety sensor with the configuration that applied with the shut
-
down. The configuration remains saved in the safety sensor.
Perform a function test (see chapter 11.3 "Periodically by the operator").
Starting up machine with safety sensor after modification or reconfiguration
If you have performed significant changes on the machine or have reconfigured the safety sensor, the
safety sensor must be checked as with the initial start-up.
Test the safety sensor (see chapter 11.1 "Before the initial start-up and following modifications").
10.6 Starting up replacement scanner unit
The replacement scanner unit and the original scanner unit must be the same with regard to the following
points:
• Scanner unit type in accordance with name plate or downward compatible with previous scanner unit
with greater range and greater function range
• Mounting on the existing connection unit
Mounting and aligning replacement scanner unit
Mount the replacement scanner unit on the connection unit instead of the original scanner unit (see
chapter 13.1 "Changing scanner unit").
Transferring configuration to replacement scanner unit
The configuration stored in the connection unit is automatically transferred to the replacement scanner
unit.
Transferring configuration with the PC
If the range and/or performance class of the replacement scanner unit is not compatible with the original
scanner unit, you must adapt the configuration of the safety sensor to the replacement scanner unit.
Connect the safety sensor's Ethernet communication interface with the PC.
NOTICE
Realignment of safety sensor not necessary!
Realignment of the safety sensor is not necessary since the replacement scanner unit is mounted on the
existing, aligned connection unit.
WARNING
Malfunctioning of safety sensor due to incorrect configuration!
The safety sensor configuration stored in the connection unit can only be adopted without changes if
the replacement scanner unit and the original scanner unit are downward compatible with respect to
range and performance class.
The replacement scanner unit will reject an invalid configuration.
Change the configuration parameters of the safety sensor using the configuration and diagnostic soft
-
ware according to the performance class of the replacement scanner unit.
Change the configuration parameters of the safety sensor using the configuration and diagnostic soft
-
ware according to the operating range of the replacement scanner unit.