Technical data and ordering data
Leuze electronic
MSI 100/200
108
Limiting continuous current
4 x 0.5 A (see Derating)
Load
Capacitive
1
Inductive
2
Max. 1
μ
F (electronic components)
- (see protective circuit)
Test pulses
<
1
ms
Protective circuit
Yes, within the scope of the operating voltage limits
Short circuit protected
Yes
Status indicator
4 x green LEDs
1
When using electromechanical components (e.g., contactors), the capacitive load can be disregarded.
2
Use a suitable and effective protective circuit on inductive loads.
Clock/signal outputs TM0 and TM1
Quantity
2
Type
Digital
Nominal voltage
24 V DC (supply via A1/A2)
Limiting continuous current
50 mA
Test pulses
~
1 ms
Short circuit protected
Yes
Times
Reaction time
Max. 30 ms (plus reaction time MSI-EM200-4RO)
See appendix "Switch-off time of the MSI 100/200 system" on page 124.
Recovery time
< 10 s
General specifications
Nominal operating mode
100% ED
Degree of protection in accordance with VDE 0470 part 1
Housing
Connection terminals
Installation location
IP20
IP20
Min. IP54
Mounting type
DIN rail mounting
Installation position
On horizontal DIN rail
Housing material
Unreinforced polyamide PA, yellow
Air and creepage distances between the circuits
Acc. to EN 50178
Degree of contamination
2
Overvoltage category
III
Maximum power loss at rated conditions
2323 mW
(with f = 8, g = 2, h = 4, I
Clock
= 50 mA, I
Out/GND
= 500 mA)
See appendix "Calculation of the power loss" on page 120
Safe digital outputs IO0 to IO3 (if configured)