Problems and solutions
Leuze electronic
MSI 100/200
98
Transmission has been interrupted during the download pro-
cedure.
1. Start transmission again.
2. If the download fails once more, remove the USB con-
necting cable from the interface on the configuration
computer and reinsert it.
3. Once the safety module has been detected correctly (see
display in the status line), restart the download proce-
dure.
Following successful project download, the MSIsafesoft safe
configuration software identifies that the checksum of the
project on the safety module does not match that of the proj-
ect on the PC. A corresponding message window is dis-
played.
Proceed as follows:
Table 12-4
Solutions for communication problems between MSIsafesoft and the safety module
Problem
Solution
Download the project to the safety
again
controller
and acknowledge by pressing the "
C
onfirm" button.
Yes
C
hecksum error
still indicated?
No
Download the project to another safety controller that is not currently
in use.
No further action
required. You can start
the function test.
Use this safety
controller
instead of the one used
first.
P
lease contact our technical support team.
C
hecksum error
still indicated?
Yes
No