MSI 100 and MSI 200 safety modules
Leuze electronic
MSI 100/200
30
3.3.4
AC-MSI-CFG1
The safety modules are equipped with a pluggable AC-MSI-CFG1 memory module.
Figure 3-7
AC-MSI-CFG1 with MSI 100/200 safety module
After downloading the configuration from MSIsafesoft to the safety module, the configuration
is stored in the AC-MSI-CFG1 memory module.
The AC-MSI-CFG1
must
be inserted in the safety module both during normal operation and
for downloading configuration data from MSIsafesoft via the USB interface.
Behavior without
AC-MSI-CFG1
If no AC-MSI-CFG1 is plugged into the safety module or if it is pulled out, the safety module
behaves as follows.
As an alternative to downloading the configuration via the USB interface, it can also be
loaded on the safety module using the AC-MSI-CFG1.
See "Loading the configuration using the AC-MSI-CFG1 memory module" on page 84.
PW
R
EXT
ERR
CF
G
A1
A1
A2
A2
24V
0V
O0-
01-
T0
T0
T1
T1
M
1
M
2
M
3
M
0
CONFIRM
CFG
STICK
MSI100
I0
I8
I4
I12
I1
I9
I5
I13
I2
I10
I6
I14
I3
I11
I7
I15
O0
I16
O1
I17
O2
I18
O3
I19
www.leuze.de/MSI
Table 3-2
Module behavior in case of missing AC-MSI-CFG1
AC-MSI-CFG1 status
Module behavior
Stick is not plugged in while downloading the
configuration data.
Configuration cannot be loaded. MSIsafesoft
outputs an error message.
Stick is not plugged in when the safety mod-
ule is started.
All outputs remain switched off. Safety mod-
ule outputs an error state. Safety module per-
forms no functions.
Stick is pulled out during running operation.
Safety module switches off all outputs and
outputs an error state. Safety module exe-
cutes no further functions.
Stick is pulled out and plugged in according
to the instructions for loading the configura-
tion.
See "Loading the configuration using the
AC-MSI-CFG1 memory module" on page 84
The safety module switches off all outputs
and executes no functions until the stick is
plugged in again correctly. The safety mod-
ule
does not indicate an error state