OPERATING
Diagnostics
This screen is designed for Lennox technicians. To access it click on the button
“diagnostic” from the start up setting page (see
Picture 26; Hydrocontrol start up Paragraph)
Buttons:
-
Welcome: To return to the home page
-
Time: To access the schedule page
-
Settings: To access the start up settings page
-
Reset: To reboot the HMI
-
Return: To access the previous page
From here you can set the HMI BACnet MS/TP address and the maximum value of the HMI address (which is the master in the
network).
Below you can see:
-
Total frame sent and received by the HMI on the network
-
Number of error (sent and received) detected by the HMI
-
The 10 minute value which is the number of the total frame sent each 10 minute (If during 10 minute the value
didn’t increase the
HMI will perform an automatic reboot)
-
Reset count: the number of ma automatically reboot performed by the HMI.
Picture55: Diagnostic page
Chiller parameters
(Climatic™)
In case a chiller is connected you will have to set the BMS connection:
3826 Address = 1
3827 Protocol = Carel
3828 Baudrate = 19200
Picture56: Chiller settings