-10-
HYDROCTROL-IOM-1903-E
OPERATING
Once you enter in the submenu list you have access to (See the end of this Paragraph):
− Unit: set here the unit in °C of °F
•
Use directly the arrow to change the value
− SYS CFG: System configuration
Use it to set the system configuration
•
Type: Choose the system type (2 Tubes/ 4 Tubes
…)
•
Ctrl: Choose the control type (Local, Master, Slave).
•
TEMPCTRL: Choose the temperature control type
•
Room: Set the room number to configure the master/slave network.
•
FAN: Choose the fan type.
•
FANM: Choose the fan functioning mode.
•
Exit
− IN CFG: Inputs configuration
Use it to set the inputs of the controller
•
SI3: Set the source of SI3
•
UI2: Set the source of UI2
•
DI4: Set the source of DI4
•
DI5: Set the source of DI5
•
DI6: Set the source of DI6
•
Exit
− OUT CFG: Outputs configuration
Use it to set the outputs of the controller
•
CLG TYPE: Set the type of the cool water valve
•
CLG NO/NC: set the direction of the cool water valve
•
HTG TYPE: Set the type of the heat water valve (only for 4 tubes)
•
HTG NO/NC: set the direction of the heat water valve (only for 4 tubes)
•
Exit