OPERATING
To change the net settings follow these instructions:
1)
Touch the field which has to be changed
2)
Change the “Auto” mode to manual by touching the Auto button:
3)
Touch the writing field and use the keypad to enter the new value
4)
Repeat the action 1 to 3 for all the field you have to change
5)
Wait 10 seconds and reset all field to auto value by touching the field
and then touching the manual button. /!\ do not change the value
6)
Press Ok to validate
If the value remains the same, the HMI did correctly take in count the new
network parameters
If you change the name of the HMI touch the button refresh once it is done. This will allow the HMI to take in count the new name of
the FCU.
Connect the HMI using a browser
If the Hydroctonrol is connected to your local network (See wirings Paragraph) you will be able to access the HMI with a web
browser. To access it enter the Hydrocontrol IP address in the URL tab of your browser. Then enter the same user and password
you are using in the HMI.