OPERATING
Chiller settings:
The chiller setting page is dynamic and depends on the chiller changeover selection (T
°in / T°out)
-
Buttons:
-
Welcome: To return to the home page
-
Times: To go to the schedule zone page (See schedule management paragraph)
-
Return: To go to the previous page
-
Chiller Water set Cool: Set here the chiller water set point in cooling mode
-
Chiller Water set Heat: Set here the chiller water set point in heating mode
-
HMI set management: flag this box to send the 2 previous set points to the chiller. If the box is flagged the chiller will use the HMI
set points. If the box is not flagged the chiller will use its own parameters
T
°in View
-
Changeover with T
°in: Cool: The chiller turns in cooling mode if the occupied FCU’s average temperature is above this setting
-
Changeover with T
°in: Heat: The chiller turns in heating mode if the occupied FCU’s average temperature is below this setting
-
Unocc low temp protection: The chiller turns in cooling mode if the unoccupied
FCU’s average temperature is above this setting
-
Unocc high temp protection: The chiller turns in heating mode if the unoccupied
FCU’s average temperature is below this setting
T
°out View
-
Changeover with T
°out: Cool: The chiller turns in cooling mode if the outside temperature is above this setting
-
Changeover with T
°out: Heat: The chiller turns in heating mode if the outside temperature is below this setting
To change the net settings follow these instructions:
1)
Touch the field which has to be changed
2)
Change the
“Auto” mode to manual by touching the Auto button:
3)
Touch the writing field and use the keypad to enter the new value
4)
Repeat the action 1 to 3 for all the field you have to change
Picture33: Chiller setting screen (T
°in view)
Picture34: Chiller setting screen (T
°out view)
Picture35: editing pop up (Auto)