-12-
HYDROCTROL-IOM-1903-E
OPERATING
− CALIB: Calibration
Calibrate the temperature, humidity and motion sensor reading. On each screen use the arrow to change
the calibration and the menu button to validate the value.
•
1st screen: Temperature calibration.
•
2
nd
screen: Humidity calibration.
•
3rd screen: Motion sensor calibration
•
Exit
− EXIT
Press one of the arrow buttons to go back to the home screen
The FCU controller can be addressed using the EC-Smart-View thermostat or using the DIP switch directly physically on the
controller. To set it directly using the DIP see appendix 2 « DIP switch position » page 32. To set the MAC address using the EC-
Smart-View enter the main menu with the password. Once you are in the main menu go to the GEN CFG menu by pressing 7 times
on the menu button and 1 time on one arrow button to enter in it. You access directly to the MAC address setting so use the arrow
to select the MAC address (10-32) then press 5 times on the menu button to access the Exit and press one arrow to validate. /!\ If
the address is set manually with the DIP you will not be able to change it using the EC-Smart-View. To reset the manual address
setting set all DIP switches in OFF position like the following:
ECB-PTU-207
Submenu
Parameter Default
Valid Choices
Description
SYS CFG
TYPE
1
CL
2 Pipes cooling
2
CL-EH
2 Pipes cooling with electric heater
3
CO
2 Pipes changeover
4
CO-EH
2 Pipes change over with electric heater
5
HT
2 pipes heating
6
HT-EH
2 pipes heating with electric heater
X
7
CL-HT
4 pipes
8
CL-HT-EH
4 pipes with electrical heater
CTRL
X
1
LOCAL
Stand alone FCU
2
MASTER
Master FCU
3
SLAVE
Slave FCU
TEMPCTRL
X
1
LOCAL
Local space temperature is used
2
MASTER
Local space temperature is used and sent
over the network
3
SLAVE
Space temperature of master controller is
used
4
AUTO
Space temperature of master controller is
used with fallback to local value
ROOM
1
0
127
Room value for master/slave network
FAN
1
NONE
Fan control not used
X
2
ECM
ECM motor (0-10V output)
3
3SP
3 Speed fan is used
FANM
1
ON
Fan control between minimum speed and
100%
2
AUTO
Fan control based on terminal load
(stopped when dead band)
X
3
SMART
Fan control based on terminal load when
unoccupied, controlled between
minimum speed and 100% in other
occupancy
1
###
###
OFF
2
###
###
OFF
4
###
###
OFF
8
###
###
OFF
16
###
###
OFF
32
###
###
OFF
64
###
###
OFF
-
EOL
EOL
DIP Switch