-18-
HYDROCTROL-IOM-1903-E
OPERATING
2)
User logged on
This screen adds the access to
-
Times/schedule menu (button times)
Moreover the word
“User” is displayed at the bottom right just above the HYDROCONTROL version number.
3)
Admin logged on
This screen adds the access to:
-
Setting menu (button settings)
The word
“User” is replaced by the “Admin”
Note: For all levels if the chiller option is disable, the chiller button will be hidden
Password management
Three main levels of password are managed by the application.
1)
No connection: It is a visualisation level. The user has access only to functioning displays. The schedule and setting displays
are hidden.
2)
User level: This is a operator level. The user has the access to schedule menus. He can change some set points, create the
schedule and add the FCU/chiller to the schedule zones.
3)
Admin level: The user has the full access to the application. He can change the HMI settings and the application settings. This
mode is required during the start up.
By default the users/passwords are:
-
user / user
-
delta / login
Picture23: Homepage (User logged on)
Picture24: Homepage (Admin logged on)