-13-
HYDROCTROL-IOM-1903-E
OPERATING
ECB-PTU-207
Submenu
Parameter Default
Valid Choices
Description
IN CFG
SI3
1
UNUSED
Not used
2
DISCH TEMP
Discharge temperature sensor connected to
this input
3
RETURN TEMP
Return air temperature sensor connected to
this input
4
WATER TEMP
Water temperature sensore connected to
this input
X
5
SPACE TEMP
Room temperature sensor connected to this
input
UI2
1
UNUSED
Not used
2
DISCH TEMP
Discharge temperature sensor connected to
this input
3
RETURN TEMP
Return air temperature sensor connected to
this input
4
WATER TEMP
Water temperature sensore connected to
this input
X
5
SETPOINT OFFSET
Setpoint offset connected to this input
DI4
1
UNUSED
Not used
X
2
WINDOW NO
Window contact normaly open
3
WINDOW NC
Window contact normaly close
DI5
1
UNUSED
Not used
2
AUX CONT NO
Auxilliary contact normaly open
3
AUX CONT NC
Auxilliary contact normaly close
4
CHG OVER HEAT
Change over contact (TRUE = Heat / FALSE =
Cool)
5
CHG OVER COOL
Change over contact (TRUE = Cool / FALSE =
Heat)
X
6
COND SENSOR NO
Condensation sensor normaly open
7
COND SENSOR NC
Condensation sensor normaly close
DI6
X
1
UNUSED
Not used
2
AUX CONT NO
Auxilliary contact normaly open
3
AUX CONT NC
Auxilliary contact normaly close
4
CHG OVER HEAT
Change over contact (TRUE = Heat / FALSE =
Cool)
5
CHG OVER COOL
Change over contact (TRUE = Cool / FALSE =
Heat)
6
OCC SENSOR NO
Occupancy sensor normaly open
7
OCC SENSOR NC
Occupancy sensor normaly close
OUT CFG
CLG TYPE
X
1
UNUSED
Cooling valve is not used
2
0-10V
0-10V cooling valve only is used
3
THERMAL
Thermal and 0-10V cool valve is used
4
ON_OFF
On/Off and 0-10V cool valve is used
5
FLOATING
Floating and 0-10V cool valve is used
CLG NO/NC
X
1
NORM CLOSE
Cooling valve is normaly close
2
NORM OPEN
Cooling valve is normaly open
HTG TYPE
1
UNUSED
heating valve is not used
X
2
0-10V
0-10V heating valve only is used
3
THERMAL
Thermal and 0-10V heat valve is used
4
ON_OFF
On/Off and 0-10V heat valve is used
5
FLOATING
Floating and 0-10V heat valve is used
HTG NO/NC
X
1
NORM CLOSE
Heating valve is normaly close
2
NORM OPEN
Heating valve is normaly open
GEN CFG
MAC
ADDRESS
10
1
126
BACnet MS/TP address of the controller
SUBNET
1
1
12
Subnet address
CONTRAST
100
0
100
Contrast value
BAUD RATE
1
9.6
BAUD = 9600
2
19.2
BAUD = 19200
3
38.4
BAUD = 38400
4
76.8
BAUD = 76800
X
5
AUTO
The BAUD will be automatically search on
the network