![Lennox HYDROCONTROL Installation, Operating And Maintenance Manual Download Page 20](http://html1.mh-extra.com/html/lennox/hydrocontrol/hydrocontrol_installation-operating-and-maintenance-manual_1877200020.webp)
-19-
HYDROCTROL-IOM-1903-E
OPERATING
The usernames and password can be change in the HMI setting (see HMI settings paragraph / User setup). Note that the admin
level is mandatory and
can’t be deleted but you can change the name and the password. All the following accounts which will be
created will have the user level.
To log in expend the menu bar and touch the Login button.
Use the drop list to select the account and enter the password using the keypad.
To log off expend the menu bar and touch the Logoff button or wait the period time define in user account.
HYDROCONTROL Start up
To setup the HYDROCONTROL application the admin password is required.
From the home page go to the setting page using the setting button.
1)
First address: Select the first address of the FCU connected to the HMI i.e. FCU addresses = 12-13-14-15
first address =
364012
2)
Number of FCUs: Select the number of fan coil connected to the HMI
3)
Changeover:
1)
Chiller: the FCU changeovers are based on the chiller changeover
2)
First FCU: the FCU changeovers are based on the changeover of the FCU which have the first address
3)
Cooling: All the FCU are forced in cooling mode
4)
Heating: All the FCU are forced in heating mode
4)
Reset FCU config: Check this flag to reset the display of the FCU according to there configuration
5)
Chiller installed: If the HMI is connected to one chiller then check this flag.
6)
Language: The HMI language will also change according the selection
7)
IP address / Subnet Mask / Gateway: You can set here the Ethernet connections
8)
DHCP: By default the HMI is not set as DHCP. must be flag for DHCP connection
9)
MS/TP: This flag must be always checked to have the BACnet MS/TP connection with the FCU and the chiller. The drop list at
the right of MS/TP flag is the MS/TP baud rate. By default the baud rate is 38400.
/!\ To change the IP / subnet / getaway setting please read the instruction on next page.
Picture25: Log in
Picture26: Log out
Picture27: Start up settings